InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-28
LOM Trip Del
[s]
Duration of Loss of Mains (LOM, i.e. Vector shift and ROCOF) protection trip. After this delay, the fault
is considered as terminated and Fault reset is possible. In case of automatic fault reset, the timer is
started.
Step:
1 s
Range:
1 - 3600 s
Default setting: 3 s
LOM Trp BO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for loss of mains protections.
Default setting: None
I>
I>, I>>
[%In]
1
st
and 2
nd
threshold for short current evaluation. The level is in percentage of NominMainsCurr.
Step:
1 %
Range:
0 - 1000 %
0 = OFF, the short current protection is disabled
Default setting: 200 %
I> Del , I>> Del
[s]
Delay for short current protection.
Step:
0,01 s
Range:
0,00 - 10,00 s
Default setting: 0,00 s
I Trp BO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for overcurrent protection.
Default setting: None
I> T
I> T Del
[s]
IDMT curve shape selection for ANSI 51 time-overcurrent protection. I> T Del is the reaction time of
IDMT protection for 200% overcurrent (when mains current = 2* NominMainsCurr).
Step:
0,1 s
Range:
0,1 - 20,00 s
Default setting: 1,0 s