Mains pro 1.6.1 Global Guide
24
LED
Color
Meaning
Status
Red
flashing
Indication of severe internal failure. Contact ComAp technical
support!
Orange
flahing
Indication of internal failure. Contact ComAp technical support!
Orange
Indication of internal failure. Contact ComAp technical support!
Green
The unit is in operation with no internal problems.
Nothing
The unit is not in operation
Alt
Orange
The function Alternative setting is activated by means of binary
switch Alt setting.
Nothing
The function Alternative setting is not activated
Dis
Orange
The unit is disabled by means of binary switch Disable
Nothing
The unit is not disabled by means of binary switch Disable
4.4 Measurement screens
Following are the examples of the measurement screens, showing values measured and evaluated by the unit:
Main measurement screen (homepage), 3-phase
application:
U: measured voltages on terminal sets
Ua, Ub and Uc. If overvoltage or
undervoltage is detected on a particular
phase, arrow symbol is displayed left of
the particular voltage value.
f: measured frequency on terminal set Ua.
If overfrequency or underfrequency is
detected, arrow symbol is displayed left of
the frequency value.
Last Trip: indication of the latest event,
which caused trip by the MainsPro unit.
See the following chapter for trip
messages explanation.
Main measurement screen (homepage), 1-phase
application (setpoint System set to 1ph):
U: measured voltage on terminal set Ua. If
overvoltage or undervoltage is detected,
arrow symbol is displayed left of the
voltage value.
f: measured frequency on terminal set Ua.
If overfrequency or underfrequency is
detected, arrow symbol is displayed left of
the frequency value.
Last trip: indication of the latest event, that
caused trip by the MainsPro unit
Loss of mains (LOM) measurement screen:
Max Vs: maximum value of measured
Vector shift since unit power-up or since
the last reset Vector shift trip.