Mains pro 1.6.1 Global Guide
47
Max switched voltage/current
250 V / 4A
Max switched power
resistive load: 1000 VA AC, 200 W DC
inductive load: 50 VA AC, 25 W DC
Rated voltage/current
resistive load: 250 V / 4 A AC
200 V / 0,1 A DC, 24 V / 4A DC
inductive load: 250 V / 2 A AC
200 V / 0,1 A DC, 24 V 3A DC
Minimum load
1 W / 1VA at U
min
> 10 V
Lifetime
1 x 10
5
cycles
Terminal tightening torque
0,4 Nm
Measurement category
III (EN 61010-1)
Appliance class
II, double insulation, the device has no protective earthing terminal
(IEC 61140)
Recommended fuse of the unit power
supply and measurement circuits
fuse 1A
Intended use according to UL508
standard
MainsPro is intended for use with switchgear and associated
equipment as per the category for Protective relays – NRGU
The unit is intended for use on a DIN rail inside a switchboard with prevention of access of non-qualified
personnel. In case of access of non-qualified personnel, it is necessary to cover the terminals by means
corresponding to the environment of the unit operation. It is possible to make the user interface accessible to the
operation staff.
11.2.1 Endurance to the power supply voltage fails
MainsPro unit withstands the power supply voltages failures of 100 ms lengths in the full range of power supply
voltage on the 85 - 265 VAC / 110 - 370 VDC terminals and at the voltage .18 - 40 VDC connected to the 8 - 40
VDC terminals. The construction of the power supply allows that the unit withstands the voltage drop down to
min 40 VAC in case that the unit was started from the AC voltage within the allowed range 85 - 265 VAC. Such
a drop of the voltage for unlimited time does not influence the unit operation.
11.3 Factory default setting of MainsPro unit
Note:
The following default setting is available from version 1.5. For older versions, different factory default
setting was applied.
Setting
Setpoint
group
Setpoint name
Value
Step
Unit
Overvoltage limit 1*)
Overvoltage delay 1
V<>
V<>
V>
V> Del
262
1.00
1
0.01
[V]
[s]
Overvoltage limit 2
Overvoltage delay 2
V<>
V<>
V>>
V>> Del
273
0.50
1
0.01
[V]
[s]
Undervoltage limit 1*)
Undervoltage delay 1
V<>
V<>
V<
V< Del
184
2.50
1
0.01
[V]
[s]