Mains pro 1.6.1 Global Guide
48
Setting
Setpoint
group
Setpoint name
Value
Step
Unit
Undervoltage limit 2
Undervoltage delay 2
V<>
V<>
V<<
V<< Del
0
0.50
1
0.01
[V]
[s]
10 minutes floating average
overvoltage*
V<>
Avg V>
0 (OFF)
1
[V]
Overvoltage hysteresis
V<>
RstV>,RstV>>
100
1
[%]
Undervoltage hysteresis
V<>
RstV<,RstV<<
100
1
[%]
Voltage asymmetry limit
Negative sequence overvoltage limit
Positive sequence undervoltage limit
Common delay of all voltage asymmetry
protections
dU
dU
dU
dU
V unb
V> neg
V< pos
dU Del
0.0 (OFF)
0.0 (OFF)
0.0 (OFF)
2.50
0.1
0.1
0.1
0.01
[%]
[%]
[%]
[s]
Overfrequency limit 1
Overfrequency delay 1
f<>
f<>
f>
f> Del
0
0
0.1
0.01
[Hz]
[s]
Overfrequency limit 2
Overfrequency delay 2
f<>
f<>
f>>
f>> Del
52.00
0.50
0.1
0.01
[Hz]
[s]
Underfrequency limit 1
Underfrequency delay 1
f<>
f<>
f<
f< Del
47.50
20.00
0.1
0.01
[Hz]
[s]
Underfrequency limit 2
Underfrequency delay 2
f<>
f<>
f<<
f<< Del
47.00
0.50
0.1
0.01
[Hz]
[s]
Overfrequency hysteresis
f<>
Rstf>,Rstf>>
100
0.1
[%]
Underfrequency hysteresis
f<>
Rstf<,Rstf<<
100
0.1
[%]
Vector shift limit
ROCOF limit
ROCOF filter
ROCOF delay
Vector shift and ROCOF evaluation delay
LOM
LOM
LOM
LOM
LOM
Vs Lim
ROCOF
ROCOF Filt
ROCOF Del
LOM Init Del
0
1
9
0.5
3
1
0.01
1
0.01
1
[°]
[Hz/s]
[-]
[s]
[s]
Vector shift and ROCOF signalization time
(TRIP duration)
LOM
LOM Trp Del
3
1
[s]
Measurement range
Basic
Uin
230
-
[V]
Measured system
Basic
System
3ph
-
-
Display timeout
Basic
DispT
0
1
[min]
Automatic Fault Reset enabling
Basic
Auto FR
ENABLED
-
-
Automatic Fault Reset timer
Basic
Auto FR Del
˃20
1
[s]
TRIP at the unit startup
Basic
Start Trip
DISABLED
-
-
Common impulse length
Basic
Imp Len
3
1
[s]
Back-up Trip Output Delay
Basic
Bak Trp Del
0.5
0.1
[s]
Enabling the external trip binary switch
Basic
Ext
ENABLED
-
-