Mains pro 1.6.1 Global Guide
51
12.1 Library of Setpoints
MainsPro provides the possibility of dual setting of the protection functions setpoints. This setting may be used
in case that the installation is running in exceptional conditions with different requirements for protections
setting. Some groups of setpoints have their alternative setpoints identified by the same name, but with latter
“A.” at the beginning (e.g. V<>, A.V<> etc.). By activating the binary switch Alt settings, the unit is immediately
switched to the setting, done in the “A.xx” group,
see Library of Binary switches on page 61
V>, V>>, V<, V<<, A.V>, A.V>>, A.V<, A.V<< [V]
V> del, V>> del, V< del, V<< del [s]
f>, f>>, f<, f<<, A.f>, A.f>>, A.f<, A.f<< [Hz]
f> del, f>> del, f< del, f<< del, A.f> del, A.f>> del, A.f< del, A.f<< del [s]
LOM Init Del, A. LOM Init Del [s]