Omega II
®
Installation, Operation & Maintenance
Page 18
Combustion Research Corporation
INSTALLATION PROCEDURE
The P/N 0366.00 side shield is used o the deep reflector.
The PN 0367 side shield is designed for use on standard,
and panel reflectors. This side shield may be installed on
either side of the reflector. Refer to the layout plan and
clearance to combustible chart on the preceding page for
proper location.
Install one ten-foot side shield in conjunction with each ten
foot section of reflector so that overlap joints align.
Cut a suitable relief notch for every reflector hanger and
support.
The side shield is to be fastened to the reflector with #8 self
drilling and tapping screws, one near each end and
approximately one every two feet. The side shield
expansion joint must match the reflector expansion joint.
DO
NOT SCREW THE EXPANSION JOINTS TOGETHER.
Reflector
Tube and reflector
hanger
Reflector
intermediate
support
Field fabricated relief
notches
Side shield
Field fab relief
notch in side
shield
Secure with
S/M screw
Secure side
shield hanger
with S/M screw
Secure side shield
support (P/N
0368.00) to tube
with S/M screw
0367.00
Side Shield
0360.00 REFLECTOR & 0367.00 SIDE SHIELD
Field fab relief
notch in shield
Secure with S/M screw
Secure side
shield hanger
with S/M screw
Secure side shield
support (P/N 0368.0010)
to tube with S/M screw
P/N 0367.00
Side shield
0812.00 REFLECTOR & 0367.00 SIDE SHIELD
Field fab relief
notch in side
Secure with
S/M screw
Secure side
shield
hanger with
S/M screw
Secure side
shield support
P/N (0366.0050)
to tube with S/M
screw
0366.00
Side shield
0363.00 REFLECTOR & 0366.00 SIDE SHIELD