Omega II
®
Installation, Operation & Maintenance
Combustion Research Corporation
Page 25
GENERAL
The requirements and practices described below are based
on the National Electrical Code ANSI/NFPA No. 70 (current
standard) and the Canadian Electric Code. Although the
requirements are uniform throughout the country, local
electrical codes may deviate from the National Electrical
Code and the Canadian Electric Code, therefore, local
inspection authorities should be consulted regarding local
requirements.
WARNING
ELECTRICAL SHOCK
DANGER OF SEVERE INJURY
OR DEATH
Field wiring to the heater and vacuum exhauster must
be connected and grounded in accordance with
national, state, provincial, local codes and to the
guidelines outlined in this manual. In the United States
refer to the most current revisions to the ANSI/NFPA
70 Standard and in Canada refer to the most current
revisions to the CSA C22.1 Part I Standard.
BURNER ASSEMBLY
Safety control circuits must be a two wire circuit with a
separate earth ground, and have a nominal voltage not
exceeding 125 volts. A safety control or protection device
must be connected so as to interrupt the ungrounded
conductor. Install a service disconnect within 3' of the
OMEGA II
®
Burner Assembly
.
The
OMEGA II
®
Burner Assembly
shall be connected to a
power supply branch circuit fused at not more than the
value appropriate for the rating of any control or device
included in the circuit.
Each
OMEGA II
®
Burner Assembly
electrical requirement
is 1.8 FLA amps at 115V, 60 Hz. The thermostat shall be
installed on the hot (L1) side with a sufficiently fused
electrical supply line.
DO NOT RUN THE ELECTRICAL
SUPPLY LINES DIRECTLY ABOVE THE REFLECTOR
OR BELOW THE REFLECTOR - CLEARANCE TO
COMBUSTIBLES MUST BE MAINTAINED.
NOTE:
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced with wiring
material having a temperature rating of at least 90°C.
Field wiring having a minimum rating of at least 90°C shall
be used and supply circuit wiring shall have a minimum size
of 14AWG.
Large enough wire must be used in connecting to the
OMEGA II
®
Burner Assembly
. This is necessary for two
reasons: 1) carrying capacity and 2) voltage drop. The
wire size necessary to provide carrying capacity without
over heating is determined by electrical codes which
specify a minimum wire size for the amperage used. Most
electrical supply problems are caused by voltage drop due
to long runs, or low voltage supplied by the utility.
The correct size wire should be carefully selected before
the installation is made. The first step is to establish what
voltage will be supplied by the utility. This will vary across
the country and should be verified by the utility and by
actual measurement of the supply voltage prior to
installation. The following chart shows maximum wire
lengths which will keep the voltage drop to a minimum of
10% at various currents at 115V. Only copper wiring
should be used.
WIRE LENGTH FOR 10% VOLTAGE DROP
IN
FEET - 115V 60HZ
COPPER WIRE SIZE
AMPERES No.14 No.12 No.10 No.
8
15
150 225 350 600
20
110 175 275 450
25 90
140
225
350
30 75
125
150
300
35 -
100
135
250
40 -
85
125
225
45 -
-
110
200
50 -
-
-
175
When supplying single phase from a three phase system,
use a suitably sized machine tool transformer to transform
460V or 230V three phase to 115V single phase. Under no
circumstances use 277V single phase input.
WARNING: Do not use 277 volt.
!
Summary of Contents for Omega II
Page 40: ...Omega II Installation Operation Maintenance Page 36 Combustion Research Corporation...
Page 48: ......
Page 49: ......