Combustion Research Corporation
Page 31
The performance of an electric motor drops rapidly as the
voltage at its terminal is reduced. A 10 percent drop in
voltage reduces its output by about 20 percent. In order to
ensure proper operation, the motor must receive as close
to nameplate voltage as possible during start-up when the
amp draw is at it's highest.
AMPERE REQUIREMENTS OF Reflect-O-Ray
®
COMPONENTS
♦
All Reflect-O-Ray
®
Oil Fired EDS 3.5 burner
assemblies - 115V - 1.6 amp (4.0 FLA)
♦
0402.WO/DI/SS - 1 HP Vacuum Exhauster FLA -
l2.4/6.7 amps 115V/230V
♦
0401.WO/DI/SS - 1/2 HP Vacuum Exhauster FLA -
5.4/3.0 amps 115V/230V
♦
0201.WO/SS - 1/4 HP Vacuum Exhauster FLA -
3.6/1.8 amps 115V/230V
♦
5487.00 - Thermostat Contact rating 16 amps – 24
VAC to 115 V.A.C.
♦
5484.00 - Thermostat Contact rating 9.8 amps – 24
VAC to 115 V.A.C.
BASIC SYSTEM HOOK-UP
WARNING
FIRE OR EXPLOSION HAZARD
IMPROPER INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE DEATH, SEVERE INJURY
AND/OR PROPERTY DAMAGE.
The thermostat must control both the Vacuum
exhauster and Burner(s).
DO NOT CONTROL
SEPARATELY
.
Burner(s)
MUST NOT be wired
"HOT".
Refer to the electrical wiring section of this
manual.
Referring to the following diagram, we see a basic
configuration that uses a line voltage thermostat to control
power supply to the vacuum exhauster and burner
transformers. Typically the burner transformers are
mounted near the vacuum exhauster.
The
THERMOSTAT DIRECTLY POWERS BOTH THE
VACUUM EXHAUSTER AND THE BURNER(S)
. Burners
must not be wired “HOT”.
Consult the factory for alternate voltage requirements.
L2
115V - 60Hz - 1 PHASE
FUSED BY OTHERS
M1
BURNER
1 POLE 15 AMP
DISCONNECT SWITCH
VACUUM EXHAUSTER
1 HP, 60 Hz, 115 VOLT
BREAKER - BY
INSTALLER
1 POLE, 115 V
THERMOSTAT
M1
LEGEND
L1
!