Reflect-O-Ray
®
Oil Fired EDS 3.5
Installation, Operation & Service
Combustion Research Corporation
Page 5
0812.00 or 0812.SS Reflector - HORIZONTAL MOUNT
MODEL
A
B
B1*
C
D
0500.R
7”
72”
25”
30”
30”
0510.R
6”
72”
25”
30”
30”
D
A
B
C
0520.R
6”
72”
25”
30”
30”
* B1 – Bottom Clearance when P/N 0304.INSUL.25 radiant tube is used
“B” Clearances (bottom) can be reduced to 15”, 25’ downstream of burner
0812.00 or 0812.SS Reflector – 30° MOUNT
MODEL
A
B
B1*
C
D
0500.R
7”
72”
25”
30”
30”
0510.R
6”
72”
25”
30”
30”
D
A
B
C
0520.R
6”
72”
25”
30”
30”
* B1 – Bottom Clearance when P/N 0304.INSUL.25 radiant tube is used
“B” Clearances (bottom) can be reduced to 15”, 25’ downstream of burner
0363.00 or 0363.02 Reflector - HORIZONTAL MOUNT
MODEL
A
B
C
D
0500.R
7”
72”
42”
42”
0510.R
6”
72”
30”
56”
D
A
B
C
0520.R
6”
72”
30”
56”
0500.R - “B” Clearances (bottom) can be reduced to 40”, 20’ downstream of burner
0510.R - “B” Clearances (bottom) can be reduced to 40”, 20’ downstream of burner
0520.R - “B” Clearances (bottom) can be reduced to 24”, 20’ downstream of burner
0363.00 or 0363.02 Reflector – 30° MOUNT
MODEL
A
B
C
D
0500.R
7”
72”
42”
42”
0510.R
6”
72”
30”
56”
D
A
B
C
0520.R
6”
72”
30”
56”
0500.R - “B” Clearances (bottom) can be reduced to 40”, 20’ downstream of burner
0510.R - “B” Clearances (bottom) can be reduced to 40”, 20’ downstream of burner
0520.R - “B” Clearances (bottom) can be reduced to 24”, 20’ downstream of burner