Reflect-O-Ray
®
EDS 6
Installation, Operation & Service
Combustion Research Corporation
VACUUM EXHAUSTER EXTERIOR MOUNTING
The
Reflect-O-Ray
®
vacuum exhauster
can be mounted
on the exterior of the building provided appropriate
weather covers are installed. The vacuum exhauster is to
be mounted bottom horizontal discharge. It is
recommended that all exterior ducting be insulated or use
double wall vent pipe. Weather covers are to fabricated
from 16 gauge hot-dipped galvanized steel. Caulk all
seams.
To accommodate expansion and vibration install the
0634.SS exhaust flex below the roofline.
Maintain a minimum of 3 feet above exhaust outlet to roof
or overhang and a minimum of 6 feet to adjoining building
or parapet. Exhaust outlet must be at least 6" (
15cm
)
above anticipated snow depth.
Page 26
Combustible Wall – Provide wall thimble
Non-Combustible wall – Seal with RTV Silicone
Weather Cover
by Installer
Install Bird Screen
In Outlet
Weather Cover
must come to
bottom of motor.
Install 0634.SS Flex on the inside of building – Use
radiant tube for wall penetration
Combustible Wall – Provide wall thimble
Non-Combustible wall – Seal with RTV Silicone
Weather Cover by
Installer
Install Bird Screen
In Outlet
Wall Mount bracket
assembly by installer
Weather Cover
must come to
bottom of motor.
Install 0634.SS flex on the
inside of the building – Use
radiant tube for wall penetration.