IE-LOG-S5141-01
5
Notice:
If logger operates as permanently connected to the computer, using of magnet start/stop
is disabled.
To enable the logger control by magnet is suitable only in cases, when possibility of
unauthorized manipulation to the logger operation is eliminated.
Connection to voltage output of a transducer
The devices with the voltage output connect to data logger by the shielded cables and the WAGO
terminals. The shielding of cables connect to (-) terminals. All (-) terminals are galvanically
connected and therefore the voltage transducers have to be powered from one source. Short change
of polarity does not cause the damage, but data logger does not measure correctly (records zero
voltage). Permanent incorrect polarity is not allowed (increased consumption from the battery).
Note:
all (-) terminals are galvanically connected in data logger.
Readings on the display in usual operation (logger switched ON)
After switching ON the logger all LCD symbols are displayed for checking
the display.
Then actual date and time in logger is displayed for approximately 4 s.
Consequently reading of estimated remaining battery capacity for
approximately 2 s is displayed (values 0 to 100%). It is valid if logger is
operated at temperature from -5 to +35°C. If logger is operated often outside
of the above temperature range battery life can be reduced to 75%, i.e. if
displayed remaining battery capacity drops below 25%, it is recommended to
replace the battery.
If display is switched ON
, actual readings of measured values are displayed.
The value from 1. channel (symbol 1) is displayed on the LCD upper line,
value from 2. channel (symbol 2) on the LCD lower line. Symbol LOG
indicates data logging in progress – if it blinks, data memory is filled up to
more than 90%.
Every 5 s display is automatically switched to displaying of measured
quantity. Logger now displays value of 3.channel (LCD upper line) and
ambient temperature (LCD lower line).