IE-LGR-Uxxxx-16
51
U0541
_________________________________________
Measured values:
2 x temperature by an external COMET Pt1000/0
probe
2 x voltage input (0
– 10) V DC.
Range:
Temperature:
(-20
0 to +260) °C, Pt1000/3850 ppm,
measuring current: approx. 0.5 mA in approx.
60 ms long pulses
Voltage: (0-10) V DC, input resistance: approx. 130 k
Input accuracy (without probes):
Temperature:
±0.2 °C in the range of (-200 to +100) °C
±0.2 % of the measurement value in the range
of (+100 to +260)
°C
Voltage: ±10 mV
The accuracy of the device with the temperature probe
connected is determined by the above input accuracy
and the accuracy of the probe used.
Connection:
Pluggable terminal block, maximum wire cross section
1.5 mm
2
. Recommended length of the Pt1000 probe
cables is maximum 15 m, a length of 30 m should not be
exceeded. Maximum length of the voltage inputs cables
is 30 m. It is recommended to use shielded cables.
CAUTION: The inputs are not galvanically isolated!
Response time:
Is determined by the response time of the used probe (it
valid if
Measuring interval
is set to 1 s).
Resolution:
0.1 °C converter range: 16 bits
Recommended calibration interval:
2 years
U2422
_________________________________________
Measured values:
Barometric pressure and the concentration of CO
2
in the air.
Ranges:
Barometric pressure (absolute): 700 hPa to 1100 hPa
Concentration of CO
2
:
0 to 1
% … probe CO2R1-x
Summary of Contents for U0110
Page 5: ...IE LGR Uxxxx 16 5 General view of a Uxxxx series datalogger U0141 model...
Page 64: ...64 IE LGR Uxxxx 16 Dimensions U0110 U0111 U0122...
Page 65: ...IE LGR Uxxxx 16 65 U0121 U0141...
Page 66: ...66 IE LGR Uxxxx 16 U0246 U0141T U0541 U5841 U6841 U7844 U2422...
Page 67: ...IE LGR Uxxxx 16 67 U3121 U3120 U4130...
Page 68: ...68 IE LGR Uxxxx 16 U3430 U4440 U3631...
Page 69: ...IE LGR Uxxxx 16 69 U8410...