background image

 

 

13 

4.6. 

 

UPS settings menu 

To enter the configuration menu, press the Test / Up + MUTE / Down buttons simultaneously for more 
than 1 second. View of the configuration menu and description of the possible settings below. 
To access all settings, the UPS should be in Stand-by mode (no voltage at the UPS output) or Bypass 
mode (parameters 15 and 16 are available while the inverter is running). 
 
Parameter 1 
Indicates the number assigned to a specific parameter as 
described below, e.g. 01 - output voltage. 
 
Parameter 2 and 3 
Indicates a value specific for a given parameter, e.g. 230 
- the value of the output voltage. 
 

Display state 

Settings 

01 - Setting the output voltage value 

 

208: Indicates 208Vac output voltage 
220: Indicates 220Vac output voltage 
230: indicates 230Vac output voltage (default) 
240: Indicates 240Vac output voltage 

02 

 The output frequency 

60 Hz, CVCF mode 

 

50 Hz, Normal mode 

 

ATO 

 

Parameter 2: The output frequency 
Allows you to select the frequency: 
50Hz: The output frequency is 50Hz 
60Hz: The output frequency is 60Hz 
ATO: autosensing. The UPS automatically detects the frequency of the 
utility voltage. 
 
Parameter 3: UPS operating mode 
CF: UPS works as a frequency converter. The output frequency value 
should be set to 50 or 60 Hz. 
NCF: The UPS works in normal mode, within the tolerance of the input 
frequency, the UPS synchronizes to the mains frequency. 
Exceeding  the  permissible  frequency  tolerance  causes  the  UPS  to 
switch to battery operation. 
 
 

Attention! In CF - frequency converter mode, the Bypass function is 
automatically blocked. 

03 - Voltage tolerance range for Bypass 

 

Parameter 2: Lower Voltage Tolerance Range for Bypass. 
The value is adjustable from 110-209V (default 110V). 
Parameter 3: High Voltage Tolerance Range for Bypass. 
The value is adjustable from 231-276V (default 264V). 

Summary of Contents for COVER CORE 10K

Page 1: ...E 6 10 kVA User manual The content of this document is the copyright of the publisher and may not be reproduced without prior permission The right to modify the design and specifications is reserved w...

Page 2: ...2 LED indicators 10 4 3 LCD display 11 4 4 Alarm signals 12 4 5 LCD display letter abbreviations 12 4 6 UPS settings menu 13 4 7 Description of the UPS operation modes 15 4 8 UPS warnings and audible...

Page 3: ...Compatibility EMC Test and Measurement Methods Radio Frequency Electromagnetic Field Immunity Test EN 61000 4 4 2004 A1 2010 Electromagnetic Compatibility EMC Test and Measurement Methods Test of immu...

Page 4: ...ircuit should be protected with an appropriate overcurrent circuit breaker The UPS has its own battery power source so there may be voltage on the output strip even though the UPS is not connected to...

Page 5: ...chanical damage shock and impact only transport the UPS in its original packaging All models of the CORE 6K and 10K power supplies are suitable for both horizontal and vertical mounting 2 1 Horizontal...

Page 6: ...ower supply and enable its stable placement in a vertical position The set of stands includes short and long connecting elements depending on the width of the UPS set In order to place the power suppl...

Page 7: ...y for the parallel operation version option 3 External battery connector 4 INTELLIGENT SLOT communication card slot LAN card AS400 RS485 5 RS 232 communication port 6 USB communication port 7 Remote E...

Page 8: ...attery modules as in the figure below If it is necessary to extend the autonomy time the power supply has the option of connecting a battery with a much larger capacity thanks to the fact that it is e...

Page 9: ...Cables should be connected and arranged in such a way that no one can accidentally disconnect them 3 4 Connection of remote EPO switch The UPS is equipped with an EPO port for connecting a remote eme...

Page 10: ...n the events that occur on the UPS e g power failure low battery level The software also allows for ongoing monitoring and logging of UPS event history RS232 and USB ports cannot be used simultaneousl...

Page 11: ...n to the previous menu page TEST UP Battery test Press and hold for more than 0 5 seconds during normal operation of the UPS to activate the test Up arrow Key to scroll up to the previous line in the...

Page 12: ...r easy reading of the UPS status UPS The status of the LEDs determines the current operating status of the power supply and is described in the table below LED Mode Bypass Line Battery Fault UPS start...

Page 13: ...tput voltage Hz output frequency Vdc battery voltage Load information Indicates the load level of 0 24 25 49 50 74 and 75 100 Indicates an overload condition Indicates a short circuit condition at the...

Page 14: ...voltage Vac 230V mains voltage Vdc battery voltage Hz mains frequency 4 4 Alarm signals Battery mode Beep every 4 seconds Bypass mode Beep every 2 minutes Overload Beep 2x second Error Continuous tone...

Page 15: ...240Vac output voltage 02 The output frequency 60 Hz CVCF mode 50 Hz Normal mode ATO Parameter 2 The output frequency Allows you to select the frequency 50Hz The output frequency is 50Hz 60Hz The outp...

Page 16: ...ault 58Hz Parameter 3 Setting the upper frequency tolerance for ECO mode Possible settings 50Hz 52Hz 54Hz default 52Hz 60Hz 62Hz 64Hz default 62Hz 08 Bypass mode settings Parameter 2 OPN Bypass allowe...

Page 17: ...le to make changes Parameter 2 Indicates the OP V output voltage Parameter 3 Indicates the UPS output voltage measured inside the UPS Using the arrow keys calibrate the value of the output voltage to...

Page 18: ...the event of a power failure or when the supply voltage is beyond the tolerance allowing the output voltage to be kept within the required tolerance the UPS switches to battery operation The beep sou...

Page 19: ...within 30 min Beeps every second 4 9 Warning codes Code Warning Code Ostrze enie 01 Batteries not connected 21 EC supply differences parallel operation 07 Battery overcharging 22 Differences on Bypas...

Page 20: ...age is too low 14 Short circuit on the inverter output 1A Reverse power at the inverter output 21 Battery thyristor short circuit 24 Inverter relay shorted 2A Charger short circuit 31 CAN communicatio...

Page 21: ...rmal operation Attention In order to obtain the maximum autonomy the batteries should be charged at least 10 hours after the first use The maximum capacity of the battery is obtained after two full di...

Page 22: ...o go to the next step 3 Switch the external Maintenance Bypass from BYPASS position to UPS position 4 To turn on the power supply start the inverter press the ON button on the UPS display and hold it...

Page 23: ...d damaging them Depending on the storage temperature the power supply should be connected at least every 6 months to charge the battery Typically the batteries are charged in 4 hours to 90 capacity bu...

Reviews: