15
13
–
Battery voltage regulation
Parameter 2: Choose “Add” or “Sub” to make battery voltage Up /
Down adjustment.
Parameter 3: Voltage regulation range 0 - 5.7V (default 0V).
14
–
Charger voltage adjustment
Parameter 2: Choose “Add” or “Sub” to make the Charger Voltage Up
/ Down adjustment.
Parameter 3: Voltage regulation range 0 - 9.9V (default 0V).
The batteries must be disconnected before calibrating.
15
–
Inverter voltage regulation
Parameter 2: Choose “Add” or “Sub” to make the Charger Voltage Up
/ Down adjustment.
Parameter 3: voltage adjustment range 0 - 6.4V (default 0V).
16
–
Adjusting the output voltage
If the output voltage cannot be identified (below 50V) in the menu it is
not possible to make changes.
Parameter 2: Indicates the OP.V output voltage
Parameter 3: Indicates the UPS output voltage measured inside the
UPS. Using the arrow keys, calibrate the value of the output voltage to
the actual value indicated by the meter. The result of the calibration is
obtained by confirming the change with the Enter key. Voltage
regulation range +/- 9V.
17
–
Setting and adjustment of the charging current
Parameter 2: Charging current 001-004 means 1.2, 3, 4 A respectively
Parameter 3: Correction of the charging current "+" or "-" by 0.1x the
set value.
For example, "+" "3" means the current is increased by +0.3A
4.7.
Description of the UPS operation modes
Operation mode
Description
LCD status
Normal
mode
(OnLine)
In all online UPSs, fans are working all the time. The only difference is with speed
rotation
–
it depends on the temperaturę and the load, but are working non stop.