2.4.3.
Service space
There are no vents on the side walls of the power supply, so no free space is required on the
side for ventilation. However, for access to the device from each side, it is recommended to
maintain min. 50 cm service space.
It is required to provide adequate space in front of the power supply for easy operation and the
possibility of drawing cold air from the environment. Recommended space from the front 80
cm. Due to the required access to the rear of the power supply as well as free air exhaust and
circulation, the recommended space from the rear of the power supply is at least 30 cm.
2.5.
Security elements
For safety reasons, it is required to install appropriate protections in the form of over-current
circuit breakers or other protection devices in the UPS supply switchboard. This chapter
provides general practical information for installation by qualified electricians. Additionally,