COVER MY SERIES – User Manual
COMEX S.A.
22
3.3.8.
Parallel operation
MY series power supplies can work in parallel with each other to increase system power or
provide redundancy. MY series power supplies can operate up to 8 devices in parallel, which
means that the maximum power of a system based on e.g. MY30K UPS is 240kVA.
In parallel operation of the UPS units, the load is evenly distributed among all operating UPS
units. In the case of a redundant system, eg N + 1, the failure of a single unit does not affect the
operation of other devices, and the system guarantees continuity of uninterrupted power
supply for the full power of the designed system.