COVER MY SERIES – User Manual
COMEX S.A.
23
4.
User manual for the power supply
This chapter contains detailed instructions on how to turn the UPS on and off, as well as switch
between the operating modes described in the previous chapters.
All the control keys and the LCD panel used to switch between the modes described below are
described in detail in Chapter 5.
During the following procedures, acoustic signals may appear.
4.1.
Power connectors
The UPS can be plugged in or disconnected from the power supply using connectors mounted
inside the UPS and accessible from the rear of the UPS. The UPS has 4 connectors shown
below - Input breaker - 4, Bypass breaker - 10, UPS output breaker - 9 and Maintenance
bypass breaker - 12 ). In the case of internal batteries, battery protection is also used (Battery
breaker - 10).
Figure 4.1. Location of the power connectors in the MY 30K power supply