COVER MY SERIES – User Manual
COMEX S.A.
25
4.3.
Procedures for switching the power supply between operating modes
4.3.1.
Switching from normal operation to battery mode
Open the rectifier power disconnect switch to disconnect the UPS power. The UPS will go into
battery operation. If the power supply is to be reconnected to normal operation, wait a few
seconds and then close the charger supply disconnect. After about 10 seconds, the rectifier
starts up and enters the normal operation mode.
4.3.2.
Switching from normal operation to bypass operation
Press the icon key
on the LCD panel, and then Confirm shutdown with OK.
Warning
In the Bypass mode, the loads are supplied directly from the mains and are not protected
against the effects of blackouts and disturbances in the mains.
4.3.3.
Switching from Bypass to normal operation
Press the icon key
on the LCD panel, and then confirm that the inverter is turned on with
the OK key. The UPS will transfer from Bypass Mode to On-Line Mode.
警告
危 险