COVER series MZ – User manual
COMEX S.A.
23
The procedure for starting the power supply is as follows:
1. Close the bypass power switch (Bypass breaker).
After a while, the LCD display initializes and the UPS starts up to the bypass mode. The bypass diode
should be green.
2. Close the power breaker.
Starting the inverter can be done in two ways, from the level of On keys on the display panel, or
using commands from the display panel.
To start the UPS with the ON keys, press and hold both ON keys for three seconds simultaneously.
The UPS will start the inverter.
To start the UPS with the help of the LCD touch screen, select the icon
. The display switches
to the on / off page. If the inverter was switched off, confirm switching on the inverter with the OK
key.
After starting the inverter, the bypass alarm is switched off.
3. Close the battery breaker located near the battery
4. Close the UPS output breaker.
The guaranteed voltage is applied to the receivers.
4.2.2.
Starting UPS with the battery pack
1. Check if the batteries are connected. Close the battery breaker located near external batteries.
2. Press the "cold start" button on the power supply located on the front panel of the power supply.
3. The inverter starts automatically, the inverter diode flashes. The output of the power supply is
switched on after approx. 60 seconds
The power supply operates in battery mode. The rectifier diode flashes red.
4.3.
Procedures for switching the power supply between operating modes
4.3.1.
Switching from normal operation to battery operation
Open the rectifier's power disconnector to disconnect the UPS. The UPS will go into battery
mode. If the power supply should be switched back to normal operation, wait a few seconds
and then close the rectifier's power disconnector. After about 10 seconds, the rectifier is started
and the normal mode is entered.
4.3.2.
Switching from normal operation to Bypass operation
Press the key with the icon
on the LCD panel, and then confirm by pressing OK.