background image

507961-01P

Page 11 of 58

Issue 1933

Improper  installation  of  the  furnace  can  result  in 

personal injury or death. Combustion and flue products 

must never be allowed to enter the return air system or 

air in the living space. Use sheet metal screws and joint 

tape to seal return air system to furnace.
In platform installations with furnace return, the furnace 

should be sealed airtight to the return air plenum. A door 

must never be used as a portion of the return air duct 

system. The base must provide a stable support and an 

airtight seal to the furnace. Allow absolutely no sagging, 

cracks, gaps, etc.
For no reason should return and supply air duct systems 

ever  be  connected  to  or  from  other  heating  devices 

such as a fireplace or stove, etc. Fire, explosion, carbon 

monoxide  poisoning,  personal  injury  and/or  property 

damage could result.

   WARNING

Return Air Guidelines

Return air can be brought in through the bottom or either 

side of the furnace installed in an upflow application. If the 

furnace is installed on a platform with bottom return, make 

an airtight seal between the bottom of the furnace and the 

platform to ensure that the furnace operates properly and 

safely. The furnace is equipped with a removable bottom 

panel to facilitate installation.

Markings are provided on both sides of the furnace cabinet 

for installations that require side return air. Cut the furnace 

cabinet at the maximum dimensions shown on Page 2.

Furnace applications which include side return air and a 

condensate trap installed on the same side of the cabinet 

(trap can be installed remotely within 5 ft.) require either a 

return air base or field-fabricated transition to accommodate 

an optional IAQ accessory taller than 14.5”. See Figure 14.

Figure 14. Optional Return Air Base

(Upflow Applications Only)

FRONT VIEW

SIDE VIEW

NOTE: 

Optional side return air filter kits are not for use with return air base.

1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.

Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. 
The size of the opening must not extend beyond the markings on the furnace cabinet.

2 To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.

Summary of Contents for 045-3

Page 1: ...llation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a licensed professional installer or equiva...

Page 2: ...ptional RAB Return Air Base 3 Bottom return air 4 Return air from both sides 5 Bottom and one side return air 2 Optional External Side Return Air Filter kit is not for use with optional Return Air Bas...

Page 3: ...507961 01P Page 3 of 58 Issue 1933 Figure 1 Parts Arrangement...

Page 4: ...following 1 Snap bushing 1 Snap Plug 1 Wire tie 1 Condensate trap 1 Condensate trap cap 1 Condensate trap clamp 1 2 Diameter debris screen 1 3 4 Threaded street elbow Check equipment for shipping dama...

Page 5: ...obtain a temperature rise within the range specified on the unit nameplate Failure to do so may cause erratic limit operation and premature heat exchanger failure This furnace must be installed so th...

Page 6: ...TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS VOIDS THE MANUFACTURER S EQUIPMENT LIMITED WARRANTY COMFORT AIRE CENTURY DISCLAIMS ALL LIABILITY IN...

Page 7: ...position of ANSI on the referenced subject which is represented only by the standard in its entirely In Canada refer to the CSA B149 Installation codes Do not install the furnace in a corrosive or con...

Page 8: ...g shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly or by ducts with the outdoors or spaces crawl or attic that free...

Page 9: ...tal louvers and grilles will have 60 to 75 percent free area Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equip...

Page 10: ...rap and drain connections and installation and service clearances 24 inches 610 mm at unit front The unit must be level from side to side Tilt the unit slightly maximum 1 2 in from level from back to...

Page 11: ...The furnace is equipped with a removable bottom panel to facilitate installation Markings are provided on both sides of the furnace cabinet for installations that require side return air Cut the furna...

Page 12: ...installed in horizontal applications with either right or left hand air discharge Refer to Figure 18 for clearances in horizontal applications Figure 18 Horizontal Application Installation Clearances...

Page 13: ...f unit is installed above finished space fabricate an auxiliary drain pan to be installed under unit Set unit in drain pan as shown in Figure 20 Leave 8 inches for service clearance below unit for con...

Page 14: ...quivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal If a filter is installed size the return air duct to fit the filter frame Pipe Fittings Specifications All pi...

Page 15: ...nutes before placing unit into operation DANGER 1 Measure and cut vent pipe to desired length 2 Debur and chamfer end of pipe removing any ridges or rough edges If end is not chamfered edge of pipe ma...

Page 16: ...he venting system being placed into operation while all other appliances connected to the venting system are not in operation WARNING Capacity VENT PIPE DIA in STANDARD CONCENTRIC Outdoor Exhaust Acce...

Page 17: ...nt pipe is probably oversized for the single water heater or other appliance The vent should be checked for proper draw with the remaining appliance Exhaust Piping Route piping to outside of structure...

Page 18: ...al in exhaust or intake terminations Doing so will cause freeze ups and may block the terminations IMPORTANT Table 4 Minimum Vent Pipe Lengths Capacity Min Vent Length 045 070 090 110 135 15 ft or 5 f...

Page 19: ...6 21 70 70 48 13 93 92 73 73 69 10 31 16 65 65 43 8 88 87 68 68 64 Standard Termination Elevation 4 501 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Capacity Capacity Capacit...

Page 20: ...8 13 60 60 44 9 76 76 69 69 60 10 23 8 55 55 39 n a 71 71 64 64 55 Concentric Termination Elevation 4 501 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Capacity Capacity Capac...

Page 21: ...53 49 10 21 6 50 50 28 68 67 48 48 44 Standard Termination at Elevation 4 501 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Capacity Capacity Capacity Capacity 45 70 90 110 1...

Page 22: ...t Applications TYPICAL EXHAUST PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON DIRECT VENT APPLICATIONS RIGHT HAND DISCHARGE SHOWN SIDE VIEW 45 MAX 45 MAX 2 2 2 2 or 2 12 max EXHAUST TRANSITION 3 2 2 EXH...

Page 23: ...Discharge Shown Intake Piping Figure 27 through Figure 30 This gas furnace may be installed in either direct vent or non direct vent applications In non direct vent applications when intake air will...

Page 24: ...ill not be obstructed by loose insulation or other items that may clog the debris screen 2 If intake air is drawn from a ventilated attic Figure 31 or ventilated crawlspace Figure 32 the exhaust vent...

Page 25: ...ons and 12 above the average snow accumulation At vent termination care must be taken to maintain protective coatings over building materials prolonged exposure to exhaust condensate can destroy prote...

Page 26: ...A 3 in N A N A N A N A 8 8 7 7 13 13 1 Refer to 99 Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook 2 Poly Propylene vent pipe PP by Duravent and C...

Page 27: ...randa porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appliances 10 0...

Page 28: ...iances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btuh 30kw 36 inches...

Page 29: ...f terminations and 6 152 mm on sidewall terminations 3 On roof terminations the intake piping should terminate straight down using two 90 elbows see Figure 36 4 Exhaust piping must terminate straight...

Page 30: ...t Concentric Wall Termination 71M80 69M29 OR 60L46 US 41W92 or 41W93 Canada Figure 42 Optional Vent Termination for Multiple Unit Installation of Direct Vent Wall Termination Figure 43 Direct Vent App...

Page 31: ...grade or average snow accumulation B Horizontal separation between intake and exhaust C Minimum from end of exhaust to inlet of intake D Exhaust pipe length E Wall support distance from top of each p...

Page 32: ...R EXHAUST LINES 12 305MM ABOVE AVE SNOW ACCUMULATION SIZE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE Figure 46 Non Direct Vent Field Supplied Wall Termination SIZE TERMINATION PER EXHAUST PIPE...

Page 33: ...ermination Drain Trap assembled Figure 49 Kit 51W18 USA 15Z70 Canada Parts Identification and Assembly Exhaust from Furnace To Termination Exhaust from Furnace To Termination Kit 51W18 is shown Figure...

Page 34: ...o not use copper tubing or existing copper condensate lines for drain line CAUTION 5 Figure 54 and Figure 55 show the furnace and evaporator coil using a separate drain If necessary the condensate lin...

Page 35: ...ion using a separate drain Piping from furnace must slope down a minimum of 1 4 per ft toward trap Figure 55 Unit with Evaporator Coil Using a Separate Drain Figure 56 Evaporator Coil Using a Common D...

Page 36: ...507961 01P Page 36 of 58 Issue 1933 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC...

Page 37: ...n in or through air ducts clothes chutes chimneys or gas vents dumb waiters or elevator shafts Center gas line through piping hole Gas line should not touch side of unit See Figure 60 and Figure 61 4...

Page 38: ...ND INSTALLED GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE Horizontal Application Right Side Air Discharge Gas Valve GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION...

Page 39: ...16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 460 41 34 1180 33 41 990 28 03 900 25 48 810 22 94 750 21 24 690 19 54 650 18 41 620 17 56 2 50 8 2 067 52 5...

Page 40: ...t switch near the furnace so that power can be turned off for servicing Table 9 Capacity Maximum Over Current Protection Amps 045B3 070B3 090C3 15 090C5 110C5 135D5 20 4 Before connecting the thermost...

Page 41: ...thermostat the wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire 63 F 35 C rise Connect a sufficiently sized wire with ground to the furnace s...

Page 42: ...s a call for dehumidification Both the passive and active dehumidification methods described above can be utilized on the same furnace Circulating Airflow Adjustments Cooling Mode The units are factor...

Page 43: ...blower remains energized until the limits are closed Fan On When the thermostat is set for continuous fan operation and there is no demand for heating or cooling a call for fan closes the R to G circu...

Page 44: ...W1 W2 Heat Call Figure 68 Indoor Blower Operation High Heat W2 Call Figure 69 Indoor Blower Operation Call for Fan Percentage of High Stage Cooling Figure 70 Indoor Blower Operation Single Stage Cool...

Page 45: ...hown by a red LED on the control board The control continuously monitors its own operation and the operation of the system If a failure occurs the LED will indicate the failure code The flash codes ar...

Page 46: ...USE INJURY OR DEATH UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES NOTE IF ANY WIRE IN THIS APPLIANCE IS REPLACED IT MUST BE REPLACED WITH WIRE OF LIKE SIZE RATING INSULATION THICKN...

Page 47: ...G MATERIAL HAVING A TEMP RATING OF AT LEAST 90 c 3 PROPER POLARITY MUST BE OBSERVED FOR FIELD LINE VOLTAGE SUPPLY IGNITION CONTROL WILL LOCK OUT IF POLARITY IS REVERSED 4 FOR TEMPORARY SERVICE REPLACE...

Page 48: ...075 1210 1370 Normal 815 980 1120 1255 720 885 1020 1135 1st Stage 595 760 865 980 Normal 540 660 785 890 485 600 695 790 GUH96T070B3M Temp Rise Speed Adjustment Heating CFM 0 0 8 w c Setting D Settin...

Page 49: ...Normal 800 945 1100 1245 720 840 970 1115 1st Stage 625 710 830 950 Normal 565 670 760 860 520 610 685 785 GUH96T090C5M Temp Rise Speed Adjustment Heating CFM 0 0 8 w c Setting D Setting C Setting B...

Page 50: ...rmal 1220 1405 1570 1795 1075 1270 1430 1635 1st Stage 935 1065 1245 1405 Normal 865 970 1145 1280 790 890 1025 1165 GUH96T135D5M Temp Rise Speed Adjustment Heating CFM 0 0 8 w c Setting D Setting C S...

Page 51: ...Allowed Allowed Allowed Allowed Norm Allowed Allowed Factory Setting Allowed 10 Allowed Allowed Allowed Allowed GUH96T090C5M 10 Allowed Allowed Allowed Allowed Norm Allowed Allowed Factory Setting Al...

Page 52: ...ight burners on this furnace Each time the thermostat calls for heat the burners will automatically light The ignitor does not get hot when there is no call for heat on these units Gas Valve Operation...

Page 53: ...nt Gas Flow Approximate Capacity Seconds for One Revolution Natural LP 1 cu ft Dial 2 cu ft Dial 1 cu ft Dial 2 cu ft Dial 045 80 160 200 400 70 55 110 136 272 90 41 82 102 204 110 33 66 82 164 135 27...

Page 54: ...reset switches are located on the front of the burner box Pressure Switch The pressure switch is located in the heating compartment on the cold end header box This switch checks for proper combustion...

Page 55: ...f power to the furnace 2 Have a shallow pan ready to empty condensate water 3 Remove the clean out cap from the condensate trap and empty water Inspect the trap then reinstall the clean out cap Cleani...

Page 56: ...on box 37 Reinstall the combustion air inducer and flexible no hub connector Reconnect the 2 pin plug to the wire harness 38 Reconnect drain tubes between flue collar and cold end header box 39 Secure...

Page 57: ...Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace...

Page 58: ...height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than...

Reviews: