8.2.4 Fan speed has been out of control diagnosis and solution
(E3)
Error Code
E3/F5
Malfunction conditions
When indoor fan speed
stay
s too low (300RPM) for certain time,
the unit will stop and the LED will display the failure.
Possible
causes
●
Wiring
error
●
Fan ass
embl
y faulty
●
Fan motor faulty
●
PCB faulty
Troubleshooting:
Shut off the power supply
and turn it on 2 minutes
later. Is it still displaying
the error code?
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
The unit operates normally.
Find the cause and
repair
. For example,
check whether the fan
is blocked or the
bearing is broken?
Check the wires of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.
No
Is
the main PCB normal
through index 1
(next page)
?
Yes
Yes
Yes
Replace the fan motor.
Is the
error extinguished?
No
Replace the main PCB
No