8.2.
8
IPM malfunction or IGBT over-strong current protection diagnosis and solution
(P0)
Error Code
P0
Malfunction conditions
When the voltage signal that IPM send
s
to compressor drive chip
is abnormal, the display LED will show “P0” and AC will turn off.
Possible
causes
●
Wiring
error
●
IPM malfunction
●
Outdoor fan ass
embl
y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Troubleshooting:
For 9K~24K:
Check the wiring between main PCB
and compressor.
Are
the wires
or
connectors broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check.
Are
the IPM
terminal resistance values uniform
?
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
Please refer to the solution of
【
Fan Speed Has Been
Out Of Control
】
malfunction
Yes
Check if the compressor resistance
values are uniform .
No
Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.
Summary of Contents for A-DVC09SF-0
Page 8: ...Service Manual DVC 09 12 18 24 SF Series 8 6 For B DVC09SF 0 For B DVC12SF 0 For B DVC18SF 1 ...
Page 9: ...Service Manual DVC 09 12 18 24 SF Series 9 7 For B DVC24SF 1 ...
Page 13: ...Service Manual DVC 09 12 18 24 SF Series 13 For A DVC24SF 1 ...
Page 14: ...Service Manual DVC 09 12 18 24 SF Series 14 4 Refrigerant Cycle Diagram ...
Page 42: ...Service Manual DVC 09 12 18 24 SF Series 42 47 P W N U ...
Page 43: ...Service Manual DVC 09 12 18 24 SF Series 43 48 N V N W ...
Page 55: ...Service Manual DVC 09 12 18 24 SF Series 55 This page intentionally left blank ...