8.2.
9
Over voltage or too low voltage protection diagnosis and solution
(P1)
Error Code
P1
Malfunction conditions
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Possible
causes
●
Power supply problems.
●
System leakage or block
age
●
PCB faulty
Troubleshooting:
Check the power supply
Check the connections and
wires
Stop the unit
No
t
within
parameters
OK
Bad
Correct the connections or
replace the wires.
OK
Replace the reactor
Bad
Bad
Replace the IPM board
Check the voltage between P
and N
Check the reactor
OK
OK
Replace outdoor main PCB
Remark:
Measure the DC voltage
between P and N port. The
normal value should be
around 310V.
P
N