508134-01
Issue 2045
Page 37 of 53
Figure 43. Condensate Trap Location
(shown with right side exit of condensation)
5’ max.
to drain
1” min.
2” max.
Trap can be installed a maximum
of 5ft. from furnace (*PVC only)
Field Provided Vent
1” min. 2” max. above
condensate drain.
*Piping from furnace must slope down a
minimum 1/4” per ft. toward trap
FurnaceCondensate
DrainConnection
From Evaporator Coil
Optional
Field Provided Vent
1” min. 2” max. above
condensate drain.
Figure 44.
Condensate Trap with Optional Overflow
Switch
Figure 45. Unit with Cooling Coil Using Separate
Drain
Drain
Field Provided Vent
1” min. 2” max. above
condensate drain.
Condensate Drain
Connection
Evaporator Drain Line
(vent required)
When combining the furnace and evaporator coil
drains together, the A/C condensate drain outlet must
be vented to relieve pressure in order for the furnace
pressure switch to operate properly.
IMPORTANT
Figure 46. Evaporator Coil Using a Common Drain
Field Provided Vent
1” min. 2” max. above
condensate drain.
Evaporator Drain Line
(vent required)
Condensate Drain
Connection