508134-01
Issue 2045
Page 29 of 53
Maximum Allowable Exhaust Vent Pipe Length (in ft.) without Insulation in Unconditioned Space for Winter Design
Temperatures Single - Stage High Efficiency Furnace
Winter Design Temperatures
1
ºF (ºC)
Vent Pipe
Diameter
Unit Input Size
045
070
090
32
°
to 21
°
(0 to -6)
PVC
2
PP
PVC
2
PP
PVC
2
PP
1-1/2 in.
25
N/A
20
N/A
N/A
N/A
2 in.
18
16
31
28
50
48
2-1/2 in.
13
N/A
24
N/A
42
N/A
3 in.
9
9
18
18
35
35
20
°
to 1
°
(-7 to -17)
1-1/2 in.
15
N/A
20
N/A
N/A
N/A
2 in.
9
8
18
16
32
29
2-1/2 in.
5
N/A
13
N/A
24
N/A
3 in.
N/A
N/A
8
8
19
19
0
°
to -20
°
(-18 to -29)
1-1/2 in.
10
N/A
15
N/A
N/A
N/A
2 in.
5
3
12
10
22
19
2-1/2 in.
N/A
N/A
7
N/A
15
N/A
3 in.
N/A
N/A
N/A
N/A
10
10
1
Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2
Poly-Propylene vent pipe (PP) by Duravent and Centrotherm
NOTE
- Concentric terminations are the equivalent of 5’ and should be considered when measuring pipe length.
NOTE
- Maximum uninsulated vent lengths listed may include the termination (vent pipe exterior to the structure) and cannot exceed
5 linear feet or the maximum allowable intake or exhaust vent length listed in Table 11A and Table 11B.
NOTE
Table 12.
Conditioned
Space
Unconditioned
Space
Exhaust
Pipe
Intake
Pipe
Conditioned
Space
Pipe Insulation
Figure 27. Insulating Exhaust Pipe in an Unconditioned Space