508183-01
Issue 2114
Page 24 of 52
NOTE
- Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE -
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm)
of horizontal run is mandatory for drainage.
NOTE
- Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
Exhaust Pipe
Horizontal
Gas Furnace
12” Min.
12” Max.
Figure 21.
Horizontal Installation Offset Requirements
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
IMPORTANT
Model
Min. Vent Length
All
15 ft. or
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
*Any approved termination may be added to the minimum
length listed.
Table 9. Minimum Vent Pipe Lengths
Use the following steps to correctly size vent pipe diameter.
045, 070,
090, 110
or 135 btuh
Standard or
Concentric?
See Table 8
Intake or
Exhaust?
1-1/2”, 2”,
2-1/2,”
or 3”
Furnace capacity?
1
Which termination?
2
Which needs most
elbows?
3
How many?
4
Desired pipe size?
5
What is the altitude?
6
Use Table 10A
through 10C to find
max pipe length.
7
Figure 22.