507715-01
Page 48 of 61
Issue 1716
Table 13.
Burner Orifice Conversion Kits at Varying Altitudes
Capacity
0 - 7,500 ft
(0 - 2,286 m)
7,501 - 10,000 ft
(2,286 - 3,048 m)
Natural to LP/
Propane
LP/Propane to
Natural
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
All
11K50+
73W80*
51W01
11K45+
* Conversion requires installation of a gas valve regulator spring which is provided with the gas
conversion Kit.
+ LP Kits include low line pressure switch.
GUH92A Pressure Switch Requirements at Varying Altitudes
Capacity
0 - 4500 ft
(0 - 1371m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045
No Change
11J09
11J10
070
090
110
135
No Change
11J11
11U68
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure
switch from 0-4500 feet (0-1371 m).
GUH95A Pressure Switch Requirements at Varying Altitudes
Capacity
0 - 4500 ft
(0 - 1371m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045
No Change
No Change
11J09
070
No Change
11J12
10U93
090
No Change
11J11
10U93
110
No Change
11J12
10U93
135
No Change
11J11
10U93
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure
switch from 0-4500 feet (0-1371 m).