background image

ComfortFlame.US.com

900555-00 NC

8

Minimum Clearances For Side Combustible Material, Side Wall 

and Ceiling

A.  Clearances from side of fireplace cabinet to any combustible 

material and wall should follow diagram in 

Figure 4

.

 

Example:

 The face of a mantel, bookshelf, etc. is made of combus-

tible material and protrudes 3-1/2" from the wall. This combustible 

material must be 4" from side of fireplace opening 

(see 

Figure 4

)

.

 

NOTE

: When installing your gas logs into a manufactured firebox, 

follow firebox manufacturer’s instructions for minimum clear-

ances to combustible materials.

B.  Clearances from top of fireplace opening to ceiling should not be 

less than 42".

INSTALLATION

Continued

Figure 4 - Minimum Clearance for Combustible to Wall

*Minimum 16" from Side Wall

Example

*

Minimum Noncombustible Material Clearances

If Not Using Mantel

NOTE

: If using a mantel, proceed to If Using Mantel. If not using a 

mantel, follow the information below.

You must have noncombustible material(s) above the fireplace opening. 

Noncombustible materials (such as slate, marble, tile, etc.) must be 

at least 1/2" thick. With sheet metal, you must have noncombustible 

material behind it. Noncombustible material must extend at least 8" 

up. If noncombustible material is less than 12", you must install the 

fireplace hood accessory (24" models only). See 

Figure 5

 for minimum 

clearances.

 WARNING: Maintain the minimum clearances. 

If you can, provide greater clearances from floor, 

ceiling and adjoining wall.

 WARNING: This appliance is equipped for either 

natural gas or propane/LP gas but not both. Gas type 

is indicated on the rating plate. Field conversion is 

not permitted.

CHECK GAS TYPE

Use the correct gas type (natural or propane/LP) for your unit. If your 

gas supply is not correct, do not install heater. Call dealer where you 

bought heater for proper type heater.

INSTALLATION AND CLEARANCES (Vent-Free Operation Only)

MINIMUM FIREPLACE CLEARANCE 

TO COMBUSTIBLE MATERIALS

Side Wall 16", Ceiling 42"

LOG SIZING REQUIREMENTS

Log Size

Minimum Firebox

Height

Depth

Front Width

Rear 

Width*

18"

17"

14"

24"

20"

24"

17"

14"

28"

21"

* Measured at 14" depth.

Carefully follow the instructions below. This will ensure safe installa-

tion into a masonry, UL127-listed manufactured fireplace or certified 

vent-free firebox.

 NOTICE: Manual control heaters may be used as 

a vented product. If so, you must always run heater 

with chimney flue damper open. If running heater 

with damper open, noncombustible material above 

fireplace opening is not needed.

Noncombustible  

Material Distance (A)

Requirements for Safe Installation

12" or more

Noncombustible material okay.

Between 8" and 12"

24" Models: Install fireplace hood accessory 

(GA6050, see Accessories, 

page 26

)

18" Model: Noncombustible material okay.

Less than 8"

oncombustible material must be extended to 

at least 8". See 

Between 8" and 12"

, above. If 

you cannot extend material, you must operate 

heater with flue damper open.

Summary of Contents for Biltmore18LTN

Page 1: ...or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage INSTALLER Leave this manual with the appliance CO...

Page 2: ...ting plate This appliance is not convertible for use with other gases WARNING Do not allow fans to blow directly intotheappliance Avoidanydraftsthatalterburner flame patterns Ceiling fans can create d...

Page 3: ...upplier s instructions if you cannot reach your gas supplier call the fire department 5 This gas log set may not be installed as a vented appliance in a bedroom or bathroom 6 Before installing in a so...

Page 4: ...mmonwealth of Mas sachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit Vent free gas product...

Page 5: ...m3 per kw of the aggregate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed through openings not furnished with...

Page 6: ...Example 2 560 cu ft volume of space x 20 51 200 maximum Btu Hr the space can support 3 Add the Btu Hr of all fuel burning appliances in the space Vent free fireplace _________Btu Hr Gas water heater _...

Page 7: ...ce in a vented configuration Check your state or local codes WARNING Aqualifiedservicepersonmustinstall heater Follow all local codes WARNING Beforeinstallinginasolidfuel burning fireplace the chimney...

Page 8: ...WARNING Maintain the minimum clearances If you can provide greater clearances from floor ceiling and adjoining wall WARNING This appliance is equipped for either naturalgasorpropane LPgasbutnotboth Ga...

Page 9: ...accessory to deflect heat away fromyourmantelshelf SeeFigures5 6and7forminimumclearances Heat Resistant Material Figure 6 Minimum Mantel Clearances Without Using Hood Minimum Non Combustible Material...

Page 10: ...er to fire place floor If not heater will move when you adjust controls Moving heater may cause a gas leak or log misplacement CAUTION Do not pick up heater base assembly bytheburner Thiscoulddamagehe...

Page 11: ...logs front to back and side to side in fireplace 6 Carefully remove logs without moving heater base 7 Mark screw locations through holes in mounting brackets see Figure 11 If installing in a brick bo...

Page 12: ...diment trap in supply line as shown in Figure 14 Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and heater Locate sedi ment trap where trapped...

Page 13: ...all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valv...

Page 14: ...in middle log 2 and front log 1 See Figure 23 for Biltmore24LTN LTP See Figure 22 for Biltmore18LTN LTP 7 Add volcanic stone around base of heater if desired Do not place any volcanic stone on logs o...

Page 15: ...g 4 Figure 21 Installing Crossover Log 5 Biltmore24LTN LTP Shown Crossover Log 4 Front Log 1 Crossover Log 5 Figure 22 Installing Crossover Log 5 and Log 6 Biltmore18LTN LTP Only Crossover Log 4 Front...

Page 16: ...age personal injury or loss of life WARNING If fireplace has glass doors never operate this heater with glass doors closed If you operateheaterwithdoorsclosed heatbuildupinside fireplace will cause gl...

Page 17: ...ot MAIN BURNER Periodically inspect all burner flame holes with the heater running All slotted burner flame holes should be open with yellow flame present All round burner flame holes should be open w...

Page 18: ...2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt see Figure 28 3 Blow air through the ports slots and holes in the burner 4 Check the injector holder located at...

Page 19: ...heat for propane LP units propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local propane LP or natural gas supplier 4 The description of the part 5 The qua...

Page 20: ...Control knob not in PILOT position 3 Control knob not pressed in while in PILOT position 4 Air in gas lines when installed 5 Depleted gas supply propane LP only 6 ODS pilot is clogged 7 Gas regulator...

Page 21: ...or replace burner orifice White powder residue forming within burner box or on adjacent walls or furniture 1 When heated vapors from furniture polish wax carpet cleaners etc may turn into white powder...

Page 22: ...alve assembly This location allows the thermostat to keep the room temperature at an ideal comfort level for most fireplace applications If positioning the thermostat sensing bulb elsewhere follow the...

Page 23: ...iable Gas Type Natural Ignition Piezo Manifold Pressure 3 5 W C Inlet Gas Pressure in of water Maximum 10 5 W C Minimum 5 W C For the purpose of input adjustment Biltmore18LTP 16 000 30 000 Btu hr Var...

Page 24: ...IT OAK MODELS BILTMORE18LTN BILTMORE18LTP BILTMORE24LTN AND BILTMORE24LTP 9 23 23 23 10 8 13 14 15 4 5 1 2 Peg positions vary according to model 11 12 19 21 21 24 22 20 6 7 25 18 23 17 16 7 Cat No Mod...

Page 25: ...Burner Orifice Injector 1 J3605 Burner Orifice Injector 1 J3607 Burner Orifice Injector 1 J3612 Burner Orifice Injector 1 14 J8089 Burner Retainer Spring 1 15 J3763 Burner 1 J3784 Burner 1 16 J3697 Th...

Page 26: ...allation of this appliance Use of non approved accessory part kit can result in poor performance and safety hazards FIREPLACE HOOD BLACK Cat No F1764 Model GA6050 For all models Helps deflect heat awa...

Page 27: ...e to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provide...

Page 28: ...nce uses Dealer name IHP reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local d...

Reviews: