Layout and Function of Logic PCB Interface 

 

 

 

 

1.  Breaker Inventory LED 

Upon first power-up, the Breaker Inventory LED will flash to indicate that there is no breaker inventory present in nonvolatile 
memory, and that a breaker inventory should be taken before the panel is put into service. When the Breaker Inventory button is 
pressed and held, this LED will light until the breaker inventory is stored in nonvolatile memory. The LED will then report the 
breaker inventory by flashing once for each breaker. 

2.  Breaker Trip LED 

The red Breaker Trip LED will light if an inventoried breaker has tripped, or if a new breaker has been turned on since the last 
breaker inventory was taken. 
 

3.  Breaker Inventory Button 

The Breaker Inventory Button, when held for more than five seconds, is used to store the breaker inventory in nonvolatile 
memory. The button may also be used to temporarily silence, indefinitely disable, or re-enable the beeper (see To Temporarily 
Silence the Breaker Trip Alarm Beeper below). 

4.  B Input Power LED 

The B Input Power LED will light when power is present on the B input bus. 

5.  A Input Power LED 

The A Input Power LED will light when power is present on the A input bus. 

6.  Reset Button 

In the unlikely event that a power anomaly or static discharge causes improper operation of the microprocessor, the Reset button 
may be used to reset the microprocessor. The breaker inventory is not affected. However, when used in combination with the 

RESET BUTTON 

(BEHIND BEEPER) 

BLUE BREAKER 

INVENTORY LED  

(BEHIND BUTTON) 

BLUE A INPUT 

POWER LED 

BLUE B INPUT 

POWER LED 

RED BREAKER 

TRIP LED 

BREAKER 

INVENTORY 

BUTTON 

Summary of Contents for Matrix 016-131-10

Page 1: ...Matrix 1RU High Power Density DC Distribution Center SETUP AND OPERATION MANUAL S E T U P A N D O P E R A T I O N M A N U A L...

Page 2: ...ed at the factory to withstand the normal rigors of shipping However you should carefully inspect the box and contents to confirm that no damage occurred in transit Most shipping carriers require noti...

Page 3: ...rack use the two holes further back on the sides of the panel 2 Install the chassis ground cable A chassis ground cable should be landed on the two studs marked Chassis Ground on the left side of the...

Page 4: ...on corresponding to the output channel to be fed viewing the front of the panel from left to right the positions are A1 A2 A3 A4 A5 A6 A7 A8 then B1 B2 B3 B4 B5 B6 B7 B8 Push until the circuit breaker...

Page 5: ...ory Button The Breaker Inventory Button when held for more than five seconds is used to store the breaker inventory in nonvolatile memory The button may also be used to temporarily silence indefinitel...

Page 6: ...is turned off the red Breaker Trip LED will turn on and the alarm beeper will sound When the breaker is turned back on the LED will turn off and the alarm beeper will silence 4 The breaker inventory...

Page 7: ...successful Panel and Breaker Rating Limitations The panel is rated for a maximum current of 300A per bus The sum of the eight distribution breakers on either side of the panel may not exceed 300A The...

Page 8: ...ine Breakers Each slimline breaker has two threaded brass screw hole features designed for extraction The breaker extraction tool is fitted with screw features designed to attach to the breaker Attach...

Page 9: ...sory controller LED status indicator only About Comm net Systems Comm net Systems Inc CSI is the leader in high power density communications power systems Comm net offers comprehensive power and commu...

Reviews: