M A T R I X  

Page 7 

To Perform a Factory Reset 

1.   To perform a full factory reset (erasing all breaker inventory and alarm settings), hold the breaker inventory button 
and momentarily tap the processor reset button. 
 
2.  Continue holding the breaker inventory button until the blue Breaker Inventory LED turns off. 
 
3.  When the breaker inventory button is released, the blue breaker inventory LED will be flashing, indicating that the 
factory reset was successful. 

Panel and Breaker Rating Limitations 

 

The panel is rated for a maximum current of 300A per bus. 

 

The sum of the eight distribution breakers on either side of the panel may not exceed 300A. 

 

The maximum rating for any single breaker position is 100A. 

 

As of the publication date of this document, the 80A and 100A Heinemann Slimline 1RU circuit breakers are not UL 
approved. 

Breaker Removal 

The Breaker Extraction Tool 

The breaker extraction tool is designed to connect to the front of the slimline 
breakers compatible with the panel.  

 

 

 

The breaker extraction tool is equipped with a magnet for convenient storage of 
the tool when not in use. 

 

 

Summary of Contents for Matrix 016-131-10

Page 1: ...Matrix 1RU High Power Density DC Distribution Center SETUP AND OPERATION MANUAL S E T U P A N D O P E R A T I O N M A N U A L...

Page 2: ...ed at the factory to withstand the normal rigors of shipping However you should carefully inspect the box and contents to confirm that no damage occurred in transit Most shipping carriers require noti...

Page 3: ...rack use the two holes further back on the sides of the panel 2 Install the chassis ground cable A chassis ground cable should be landed on the two studs marked Chassis Ground on the left side of the...

Page 4: ...on corresponding to the output channel to be fed viewing the front of the panel from left to right the positions are A1 A2 A3 A4 A5 A6 A7 A8 then B1 B2 B3 B4 B5 B6 B7 B8 Push until the circuit breaker...

Page 5: ...ory Button The Breaker Inventory Button when held for more than five seconds is used to store the breaker inventory in nonvolatile memory The button may also be used to temporarily silence indefinitel...

Page 6: ...is turned off the red Breaker Trip LED will turn on and the alarm beeper will sound When the breaker is turned back on the LED will turn off and the alarm beeper will silence 4 The breaker inventory...

Page 7: ...successful Panel and Breaker Rating Limitations The panel is rated for a maximum current of 300A per bus The sum of the eight distribution breakers on either side of the panel may not exceed 300A The...

Page 8: ...ine Breakers Each slimline breaker has two threaded brass screw hole features designed for extraction The breaker extraction tool is fitted with screw features designed to attach to the breaker Attach...

Page 9: ...sory controller LED status indicator only About Comm net Systems Comm net Systems Inc CSI is the leader in high power density communications power systems Comm net offers comprehensive power and commu...

Reviews: