ADCP-90-606 • Rev C • May 2020
Page 16
© 2020
CommScope
. All Rights Reserved.
Figure 12. Mounting the Panel in a Rack
6. Connect a grounding wire to the panel in either of the two locations shown in
using the two screws and star washers provided. A two-hole grounding lug (not provided)
is recommended for this connection.
Figure 13. Grounding the Rapid Fiber Panel
Note:
When mounting the panel, provide at least 3 inches (7.6 cm) of clearance at the
panel’s rear side, as shown in
to allow the spool to rotate freely when unwound.
Note:
Ground the unit to the local facility CBN (Common Bonding Network) or IBN
(Isolated Bonding Network) per local practice.
25782-A
12-24 SCREW
AND WASHER
(4 PLACES)
PROVIDE AT LEAST 3 INCHES (7.6 CM) OF
CLEARANCE AT THE REAR SIDE OF THE
PANEL TO ALLOW THE SPOOL TO ROTATE
FREELY AS THE CABLE IS UNWOUND
3 INCHES
26194-A
GROUNDING
LOCATIONS
NOTE: FRONT GROUNDING IS NOT
AVAILABLE WHEN THE MOUNTING
BRACKETS ARE INSTALLED IN THE
2-INCH RECESS POSITION
FRONT
REAR