ADCP-90-606 • Rev C • May 2020
Page 11
© 2020
CommScope
. All Rights Reserved.
pulling eye for use in paying out the cable. The stub end non-functional connectors are of
similar construction and appearance as MPO connectors, and also equipped with pulling
eyes, only the connectors are not connected optically and are designed to be cut off after
the cable is paid out. Each fanout assembly and NG4access cabled module is equipped
with a pulling sock.
1.3
Specifications and Dimensions
lists specifications the 3RU and 4RU Rapid Fiber Panel.
shows dimensions.
Table 1. Rapid Fiber Panel Specifications
PARAMETER
SPECIFICATION
REMARKS
Mechanical
Dimensions (HxWxD)
3RU
4RU
5.25 x 17.42 x 14.73 in.
7.0 x 17.42 x 14.73 in.
(13.3 x 44.24 x 37.4 cm)
(17.8 x 44.24 x 37.4 cm)
Weight
3RU
26.5 lb. (12.0 kg)
With 100 ft. of
two
dual 12-fiber
microcables or with 200 feet of
one
dual 12-fiber microcable
4RU
37.7 lb. (17.1 kg)
With 100 feet of dual 12-fiber
microcable or with 75 feet of
single 24-fiber microcable
Mounting rack
19-inch or 23-inch
EIA or WECO
Recess options
2, 4, or 5 inches (5.08, 10.16, or 12.7 cm)
Number of ports per RU
12 (SC or LC), 24 (SC or LC), or 48 LC
Front panel connectors
3RU
4RU
SC (72 fibers maximum); LC (144 fibers maximum)
SC (144 fibers maximum)
or LC (288 fibers maximum)
Microcable
Single-mode RBR, multimode OM4,
or Indoor/Outdoor
Maximum pull force
40 lbs. (18.14 kg)
Pulling eye diameter (MPO
connector)
0.72 in. (1.83 cm)
2 pulling eyes can be pulled
through a 1.1 in. (2.8 cm) diame-
ter opening
Microcable far-end
connectors
MPO, stub, fanout with SC or LC (24 fibers maxi-
mum)
MPO (receptor); single-mode SC
(UPC or APC); single-mode LC
(UPC or APC); multimode SC or
LC (UPC)
NG4access LC cabled module
one 24-fiber LC (UPC or APC);
or two 12-fiber SC (UPC or
APC)