ADCP-90-606 • Rev C • May 2020
Page 39
© 2020
CommScope
. All Rights Reserved.
Figure 51. Removing Blue Tape
3. Using the hand wrap method as shown in
, pull all of the microcables at the same
time, causing the internal spools and attached bulkhead panels to rotate. Provide at least 3
inches (7.6 cm) of clearance at the rear side of the panel to allow the spool to rotate freely
as the cable is unwound.
Figure 52. Hand-Wrap Method for Pulling Cable
4. After paying out cable as required, do the following for each RapidReel cable spool tray:
Caution:
Use care and avoid using excessive force when unwinding microcable from the
internal spool. If the cable fails to unwind, check for obstacles or obstructions that would
prevent the spool from turning. The maximum recommended pull force that may be applied to
the pulling eye or the cable is 40 lbs. (18.14 kg)
.
25940-A
BLUE
TAPE