Technical Publication
(Continued)
Visit www.commscope.com/andrew for complete specifications on all the products listed
Bulletin # 7694293 Rev. A
12
Grounding
Ground kits required at the top and bottom
before entering the shelter / cabinet
Ground Kit UG12158-15B4-T is a universal
solution for all HFF trunk cables.
Only use Tin Plated grounding kits
Removing Jacketing for Grounding Kit installation
1. Score the jacketing 360º
2. Measure 2 inches (51 mm) and repeat
3. Identify where the aluminum shielding overlaps, this will feel like a flat spot in the cable
4. With a knife flat on the cable remove a section of jacketing between score marks
5. Lift edge of jacketing with knife tip
6. Grab lifted edge of jacketing with a pair of pliers and roll on the cable
7. Remove excess adhesive with a piece of emery cloth
Scan to
view video