HR300 SERIES DEHYDRATOR USER GUIDE MANUAL

 

 

Page 

6

 of 

12

 

 

Section 4 

Description 

The HR300 dehydrator system is designed for 
continuous automatic operation.  It is a heat 
regenerative desiccant dehydrator designed to 
operate on   -48 / -60 V DC.  The desiccant 
automatically regenerates by periodic heating 
and requires no scheduled maintenance.  It will 
supply up to 300 liters per hour (10.6 scfh) of air 
with a dew point of better than 

45°C (

49°F) at 

a nominal pressure of 3 kPa (0.44 psig). 

The HR300 is designed for mount in a standard 

19” equipment rack and has an option for ETSI 

N3 rack-mounting with adapter plates (sold 
separately).  The HR300 requires 2 rack units to 
mount. 

 
 
 
 
 

 
 
 
 
 

Dry air is supplied to the transmission lines by 
four independent outlets located on the rear of 
the chassis. 

Ambient air is drawn through desiccant beds by 
two low power diaphragm compressors.  The 
adsorbent material in the desiccant canisters 
removes moisture from the ambient air prior to 
passing it through the internal manifold where 
the system pressure and humidity level 
(optional) is monitored. 

System pressure dictates demand and the 
HR300 will respond by changing the speed of 
the compressors allowing the dehydrator to 
function without pressure switches or 
regulators.  This increases compressor life and 
overall unit reliability. 

 

 

Section5 

Installation 

5.1 

Unpacking 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The HR300 includes all necessary brackets and 
electrical terminations to successfully install the 
unit in a site. 

Installation of the HR300 requires the following 
tools: 

 

#1 and #2 Phillips head screw drivers 

 

Wire cutters and wire strippers for 
alarm terminations 

J2 Alarm Connection 

4 OUTPUT PORTS 

-48/-60 DC POWER CONNECTOR 

Summary of Contents for HR300 Series

Page 1: ...Page 1 of 12 HR300 SERIES DEHYDRATOR USER MANUAL Bulletin AE01B A0595 002 Rev A 2015 CommScope Inc All rights reserved 07 15 ...

Page 2: ...on 6 5 1 Unpacking 6 5 2 Mounting 7 5 2 1 19 Rack Mounting 7 5 2 2 Wall Mounting 7 5 3 Electrical Connections 7 5 3 1 Power Connections 8 5 3 2 Power Connections 8 5 4 Pneumatic Connections 8 5 4 Operation 8 5 6 Alarms 9 Section 6 Corrective Maintenance and Spare Parts 9 Section 7 Outline 10 Section 8 Customer Service 10 8 0 Introduction 10 8 1 In Case of Trouble 11 8 2 Initial Steps by CommScope ...

Page 3: ... must be located such that only authorized personnel have access CAUTION The HR300 utilizes heat to regenerate the drying canisters Mount the HR300 at the top of the equipment rack if possible Should be placed in the top of the equipment rack with nothing mounted above it A minimum gap of at least one rack unit should be left unused above the dehydrator Section 2 Safety Information Make sure that ...

Page 4: ...gh Humidity Alarm 10 RH optional sold separately LED Indications Power on Alarm codes Acoustic Noise 50 dBA Enclosure Degree of Protection IP20 Operating Temperature 5 C to 50 C 23ºF to 122ºF Storage Temperature 40 C to 70 C 40 F to 158 F Power Supply Std 48 60 V DC Power Consumption 45 W Dimensions 2 RU 428 mm x 87 mm x 305 mm 16 85 in x 3 43 in x 12 0 in European Community Directives CE Safety N...

Page 5: ...r B 2 Mounting Brackets B1 6 M4x10 PPH Screws SST Pass B2 6 M4 Flat Washer SST Pass C 1 Power Cable D 30 5 m 100 ft 9 5 mm 3 8 Output Tubing Additional Accessories sold separately HR300 KIT ETSI HR300 ETSI N3 RACK BRACKETS KIT HR150 KIT ACDC HR300 AC TO 48 V DC POWER CONVERTER KIT MT HR KIT HUMIDITY Humidity Sensor Kit ...

Page 6: ...t outlets located on the rear of the chassis Ambient air is drawn through desiccant beds by two low power diaphragm compressors The adsorbent material in the desiccant canisters removes moisture from the ambient air prior to passing it through the internal manifold where the system pressure and humidity level optional is monitored System pressure dictates demand and the HR300 will respond by chang...

Page 7: ...k is not included 5 2 2 Wall Mounting Install the standard 19 rack brackets on the rear of the chassis with the included screws as illustrated below The brackets will provide enough clearance for the tubing and electrical connections Secure the unit to the wall using appropriate fasteners for the wall material The hardware for mounting to the wall is not included 5 3 Electrical Connections Caution...

Page 8: ...orrect have it reversed and then re connect to the dehydrator The HR dehydrators are equipped with reverse polarity protection but will not operate under reverse polarity Polarity for the power cable is Red Positive Black Negative White Ground 5 3 2 Alarm Connections Alarm wiring will need to be provided by the customer at the installation site 5 4 Pneumatic Connections The HR300 has a quantity of...

Page 9: ...ith an LED on the front panel for a visual indication of alarm conditions A green LED indicates all is well with the dehydrator A solid or blinking amber LED indicates a problem with the dehydrator Blinks Alarm Description Solid Amber System Failure Indicates a failure of the controller Replacement will be necessary 1 High Humidity optional Indicates output air is above 10 RH This can be caused by...

Page 10: ...ounting Section 8 Customer Service 8 0 Introduction CommScope provides in warranty and out of warranty repairs as well as dehydrator and compressor overhauls from several Repair Centers Coordination of these services is provided through the nearest Sales Office or Customer Service Center The Center is also prepared to help you with the following Technical Assistance Troubleshooting ...

Page 11: ...uble If the pressurization equipment is suspect they will ask for your unit Model Number and Serial Number check the warranty status of the unit advise the availability of a loaner unit provide an estimate of the cost for inspection and repairs if the unit is out of warranty fax a Return Material Authorization Sheet to you 8 3 Repair Center Process A method of Payment must be provided prior to iss...

Page 12: ...Name and RMA XXXXXXX on outside of the box Address the box to the following Ship To Address CommScope Pressurization Service Center RMA XXXXXXX 11312 S PIPELINE RD EULESS TX 76040 6629 Please note Units received with Biological animal contamination will be returned unrepaired or scrapped after notification and you will be invoiced for inspection and freight CONTACT NUMBERS If you have any question...

Reviews: