ADCP-93-095 • Rev B • April 2018
Page 12
© 2018, CommScope, Inc.
Figure 9. Recommended Breakout Dimensions for Stranded Cable
5.4
Installing a Cable Clamp
Every LSX panel is shipped with a cable clamp that can be used to secure a cable to the chassis.
This section contains instructions for the 7-inch and 9-inch high panels. For other panel heights,
refer to the instructions provided in the cable clamp kit.
To install the cable clamp, use the following procedure. Refer to
for the 7-inch panel
and
1. Install the cable clamp bracket on the clamp mount plate using two #12-24 screws. Be sure
to position the cable clamp bracket corresponding to the note above.
2. Place the two standoffs in the standoff mounting holes in the cable clamp bracket.
Note:
The figures show the cable clamp bracket positioned for cable routing from above
the panel. For cable routing from below the panel, turn the cable clamp bracket upside
down compared to how it is shown in the figure and use the mounting holes designated in
the figure as “for under floor cable entry.”
Note:
There are four standoff mounting holes. Either the two left holes or two right holes
can be used together, not the two in the middle. Do not mount two cables side by side.
IFC
CABLE
EXPOSED
RIBBON LENGTH
(DIMENSION A)
BREAKOUT LENGTH
(DIMENSION B)
23558-A
Chassis Hei
g
ht
Dimension A
Dimension B
1.75 in.
12.0 in. (+0.0/-1.0 in.)
30.5 cm (+0.0/-2.5 cm)
38.6 in. (+0.0/-6.0 in.)
96.5 cm (+0.0/-15.0 cm)
3.5 in.
12.0 in. (+0.0/-1.0 in.)
30.5 cm (+0.0/-2.5 cm)
45.5 in. (+0.0/-6.0 in.)
113.75 cm (+0.0/-15.0 cm)
7 in., 9 in.
12.0 in. (+0.0/-1.0 in.)
30.5 cm (+0.0/-2.5 cm)
94.0 in. (+0.0/-1.0 in.)
238.8 cm (+0.0/-2.5 cm)