background image

ADCP-93-080 • Rev B • April 2018

Page 5

© 2018, CommScope, Inc.

2.2 Two Cables Per Entry Port (Figure 2B)

Use this procedure to install a second cable.

1. Cut out the appropriate size openings in the grommet that is the closest in size 

to the outside diameter for the cable being installed.

2. Attach the second set of clamp yokes to the clamp already in position. 

a. Place the spacer bracket over the bolt heads of the first clamp. Ensure the 

bolt heads are aligned to allow the bracket to slide over the bolt heads. 

b. Thread a male/female bolt through the top holes of the second set of clamp

 

yokes into the top male/female bolt of the first clamp. Do not tighten at 

this time. 

3. Route the cable through the hole cut in the grommet and into the cable clamp. 

Use split grommets as required to assure a tight fit. Thread the lower bolt 

through the bottom holes of the clamp yokes. Check that the spacer bracket is 

in place and tighten both bolts.

Note: 

Do not remove the spacer bracket after the bolts are tightened.

4. Connect the ground straps to the cable terminating and grounding plate as 

shown in 

Figure 3

.

2.3 Three Cables Per Entry Port (Figure 2C)

Use this procedure to install a third cable.

1. Cut out the appropriate size openings in the grommet that is the closest in size 

to the outside diameter for the cable being installed.

2. Attach the third set of clamp yokes to the clamp already in position. 

a. Place the spacer bracket over the bolt heads of the second clamp. Ensure 

the bolt heads are aligned to allow the bracket to slide over the bolt heads. 

b. Thread a male/female bolt through the top holes of the third set of clamp

 

yokes into the top male/female bolt of the second clamp. Do not tighten at 

this time.

3. Route the cable through the hole cut in the grommet and into the cable clamp. 

Use split grommets as required to assure a tight fit. Thread the lower bolt 

through the bottom holes of the clamp yokes. Check that the spacer bracket is 

in place and tighten both bolts.

Note: 

Do not remove the spacer bracket after the bolts are tightened.

4. Connect the ground straps to the cable terminating and grounding plate as 

shown in 

Figure 3

.

Summary of Contents for OSP-CLPFEC-LG

Page 1: ...p to three cable clamps can be assembled together for securing up to three cables in a Fiber Entrance Cabinet FEC Revision History ISSUE DATE REASON FOR CHANGE 1 05 1997 Original 1 05 1999 Updated to current format 1999 1 06 2008 Updated to current format 2007 Rev B April 2018 Updated to CommScope format and contact info updated Related Publications Listed below are related manuals and their publi...

Page 2: ... Grommets 0 80 0 90 1 00 and 1 10 inch 3 each size Clamp Yokes 6 Male Female bolt 6 Spacer bracket 2 The OSP CLPFEC LG kit uses special male female bolts and spacer plates to provide for three tier stacking Male female bolts thread into each other to accomplish the stacking The spacer plates have two cutout slots the size of the bolt head The slots keep the bolts from turning as the next bolt is t...

Page 3: ... TERMINATING AND GROUNDING PLATE SPACER BRACKETS SPACER BRACKET CABLE CLAMPS CABLE CLAMPS CABLE CLAMP GROMMET CUTOUT NOT USED GROMMET CUTOUTS NOT USED GROUND TERMINATION POINTS CABLE TERMINATING AND GROUNDING PLATE GROUND TERMINATION POINTS ADCP 93 080 Rev B April 2018 Page 3 2018 CommScope Inc Figure 2 Three Tier Clamp Configurations ...

Page 4: ...ze to the outside diameter for the cable being installed 2 Insert the grommet into the cable entry slot Start with the top groove first and press the grommet into the slot 3 Attach a set of clamp yokes to the cable termination and grounding plate with male female bolts Thread in the top bolt only at this time Do not tighten 4 Route the cable through the hole cut in the grommet and into the cable c...

Page 5: ...ket after the bolts are tightened 4 Connect the ground straps to the cable terminating and grounding plate as shown in Figure 3 2 3 Three Cables Per Entry Port Figure 2C Use this procedure to install a third cable 1 Cut out the appropriate size openings in the grommet that is the closest in size to the outside diameter for the cable being installed 2 Attach the third set of clamp yokes to the clam...

Page 6: ...OMER INFORMATION AND ASSISTANCE To find out more about CommScope products visit us on the web at www commscope com For technical assistance customer service or to report any missing damaged parts visit us at http www commscope com SupportCenter ...

Reviews: