2. Route cables to chassis securing cables to rack per local practices.
3. Assemble grommets and cable clamps on fiber cables as shown in
Figure 7
.
Figure 7. Cable Clamp Installation (LC to MPO Connector)
4. Cable clamps and several grommets are provided with the cable clamp kit for securing
cables to the chassis. More than one grommet may be needed to secure cables in the clamp.
5. Adjust cables leaving an 8-inch (20 cm) service loop within the chassis, this allows blades to
be withdrawn. Tighten compression fitting screws to secure cables at the cable entry location.
6. Connect cables to the back of the blade:
a. Leave blade fully inserted in the chassis when connecting MPO connectors to MPO to
LC adapters.
b. Before connecting MPO connectors to MPO to MPO adapters pull blade out to the
second detent.
7. Use Mille-Ties to secure cables to cable tie clip. See
Figure 8
. Use Mille-Ties to bundle
cables together as necessary.
8. Close blade after installing Mille-Ties.
24753-B
USE GROMMET FOR
SMALLER NUMBER
OF CABLES
SCREWS
COVER
PLATE
CABLE
CLAMP
CABLE TIE
CLIP
8-INCH
(20 CM)
SERVICE
LOOP