ADCP-92-309 • Issue 4 • July 2016
Page 17
© 2016
CommScope
. All Rights Reserved.
7. Adjust cables leaving an 8–inch (20 cm) service loop within the chassis, this allows blades
to be withdrawn. See
Figure 13
. Tighten compression fitting screws to secure cables at the
cable entry location.
Figure 13. Cable Installation
8. Connect cables to the back of the adapters:
a. Pull blade out to the second detent.
b. Route fibers from the fanout to the adapters.
c. Remove the ferrule dust cap from one of the patch cord connectors and then clean the
connector as specified in the Optical Fiber Connector Wet and Dry Cleaning
Instructions (ADCP-90-159) or by locally approved procedures.
d. Insert connector into the adapter.
e. While holding fibers in place slide blade cover into slot. Pull cover to the front of the
blade and latch in place. See
Figure 14
.
9. Close blade.
Caution: Always allow sufficient fiber length to permit routing without severe bends. Non bend-
optimized fibers may be permanently damaged if bent/curved to a radius of less than 1.5 in.
(3.81 cm).
24917-A
CABLE
CLAMPS
MILLE-TIES
FANOUT
FIBER
BREAKOUT
8-INCH
(20 CM)
SERVICE
LOOP