5.1
Mounting the Panel on the Equipment Rack
The Rapid Fiber Panel can be mounted in either a 19-inch or 23-inch rack or cabinet. Use the
following procedure to mount the panel, referring to
Figure 9. Mounting Bracket Installation
1. Determine if the rack or cabinet width is 19 or 23 inches. Also, determine recess required
(2, 4, or 5 inches) for mounting the panel. Refer to
.
2. If the panel is being installed in a 23-inch rack or cabinet in other than the 5-inch recess
position, remove the 23-inch mounting brackets and re-install them at the required (2- or
4- inch) recess position, as shown in
3. If the panel is installed in a 19-inch rack or cabinet, remove the 23-inch mounting brackets
and install 19-inch brackets at the required recess position, as shown in
.
4. Secure the panel to the rack or cabinet using the four #12-24 screws and #12-24 lock
washers provided, as shown in
5. Connect a grounding wire to the panel in either of the two locations shown in
using the two #10-32 screws and star washers provided. A two-hole grounding
lug (not provided but shown here for reference) is recommended for this connection.
Note:
If a Rapid Fiber Panel is installed above or below a non-Rapid fiber panel, 1RU of
open space must be left between the two panels. This space is required for accessing the rear
connectors if cleaning is required.
Note:
Ground the unit to the local facility CBN (Common Bonding Network) or IBN
(Isolated Bonding Network) per local practice.
BRACKET FOR
19-INCH RACK
BRACKET FOR
19-INCH RACK
BRACKET FOR
23-INCH RACK
5-INCH
RECESS
2-INCH
RECESS
4-INCH
RECESS
26144-A
BRACKET FOR
23-INCH RACK
8-32 SCREW (2 PLACES)
TIGHTEN TO 15 INCH-LBS
(1.7 Nm) OF TORQUE