TECP-90-814 • Rev C • October 2020
Page 44
© 2020
CommScope
. All Rights Reserved.
Figure 57. Installing Front Port Designation Plate
8 BULKHEAD ADAPTER ACCESS PROCEDURE AND SERIAL NUMBER
LOCATIONS
8.1
Accessing the Bulkhead Adapter Rear Connectors
If required, the adapter bulkhead may be moved forward to access the connectors at the rear of
the adapter bulkhead. This should only be done following
initial installation
of the Rapid Fiber
Panel and only if testing indicates that
a connector may require cleaning
. Use the following
procedure to access the connectors at the rear of the adapter bulkhead:
1. Using the red latch, carefully pull the adapter bulkhead forward until the stop position is
reached. See
2. Locate the optical connector that requires cleaning and carefully disconnect it from the
rear side of the bulkhead adapter.
3. Clean the connector as described in the Optical Fiber Connector Wet and Dry Cleaning
Instructions (ADCP-90-159).
4. Reinsert optical connector into bulkhead adapter and retest as specified by local practice.
5. When testing indicates satisfactory connector performance, carefully slide the adapter
bulkhead back into its operational position.
Note:
When accessing rear connectors for cleaning, if a non-Rapid fiber panel is installed
above or below there needs to be 1RU of space.
FRONT PORT
DESIGNATION
PLATE
FRONT
DESIGNATION
CARD
26163-A
TAB (2X)