Instruction Sheet
www.commscope.com
Page 12 of 21
Step 4D – InstaPATCH Plus Module Application
Note: InstaPATCH
or
ReadyPATCH
cables use
SYSTIMAX
shelf mounted bracket (SMB) kit or rack mounted
bracket (RMB) kit per instructions provided in 860448471 and 860380781 respectively.
1. Starting at location A (the left-most position), plug module into bulkhead cutout, as shown in figure above.
2. Mate MPO connector(s) on module with those on trunk cable or ruggedized fan out.
3. Dress cable(s) thru fiber management rings, approximately as shown. Create loops with cable, where
appropriate, to manage excess slack.
4. Repeat items 1 through 3 for all remaining positions.
Note
: If desired, splice organizer management panel assembly may be easily removed since it is not used in
this application. To accomplish this, remove 4 screws at base of the door support bracket. It may also be
beneficial to temporarily remove some of the fiber management rings if they interfere with module insertion or
extraction. Simply grasp rings firmly and pull in an upward motion until they pop out.