www.commscope.com
860543388
Instruction Sheet
Page 3 of 19
The iPatch upgrade kit is ready to use on these G2, MP and HD shelves:
Material ID
Part No.
Description
760193771
360G2-1U-MOD-SD
360G2 1U sliding modular cassette shelf
760193854
360G2-2U-MOD-SD
360G2 2U sliding modular cassette shelf
760193904
360G2-1U-MOD-IS
360G2 1U internal sliding IP360 shelf
760193763
360G2-1U-MOD-FX
360G2 1U fixed modular cassette shelf
760193847
360G2-2U-MOD-FX
360G2 2U fixed modular cassette shelf
760193888
360G2-4U-MOD-FX-16
360G2 4U fixed modular cassette 16 slot shelf
760193755
360MP-1U
360 MP-1U panel
760193920
360MP-2U
360 MP-2U panel
760193862
360MP-4U
360 MP-4U panel
760173674
360G2-1U-MOD-UHD
360G2 1U modular cassette shelf, accepts 4 modules
760173682
360G2-2U-MOD-UHD
360G2 2U modular cassette shelf, accepts 12 modules
760173690
360G2-4U-MOD-UHD
360G2 4U modular cassette shelf, accepts 24 modules
760209940
HD-1U
High-density 1U sliding modular cassette shelf, accepts 4 modules
760209957
HD-2U
High-density 2U sliding modular cassette shelf, accepts 8 modules
760209965
HD-4U
High-density 4U sliding modular cassette shelf, accepts 16 modules
760227306
UD-2U
Ultra-density 2U sliding modular cassette shelf, accepts 12
InstaPATCH
®
360 modules or MPO panels (up to 144 duplex LC ports
or 96 MPO ports)
760227314
UD-4U
Ultra-density 4U sliding modular cassette shelf, accepts 24
InstaPATCH
®
360 modules or MPO panels (up to 288 duplex LC ports
or 192 MPO ports)
Important: Limits for iPatch shelf and panel connections:
•
iPatch
MPO fiber shelves are limited to a maximum number of rack units (RUs) and will not support a fully
populated rack or cabinet.
iPatch
MPO fiber shelves support a total of 52
iPatch
MPO kits (26 rows) per
rack/cabinet, such as configured for (26) 1U shelves, (13) 2U shelves, (8) 2U UHD or UD shelves, (6) 4U
shelves, (4) 4U UHD or UD shelves, or any combination thereof. Installed
imPower
power extender will
support additional
iPatch
kits, up to two times the number of kits.
•
iPatch
MPO fiber shelves are limited to a maximum number of five (5) panels per panel bus male connector.
Start a new panel bus chain with every sixth panel in the rack system.
•
Do not mix MPO and LC
iPatch
kits in the same row of a rack.
•
When mixing
iPatch
copper and fiber kits in a single rack, observe the following power worksheet formulas:
Adding all kit types multiplied by factor should total
≤ 10,000
imVision only
ImVision with imPower
Number of iPatch kits
factor by
# of HD fiber modules
x 138
# of CU kits
x 222
# of 1U G2 LC kits
x 222
# of 96F LC or MPO kits
x 94
Maximum no. of kits in rack
≤ 10,000
Number of iPatch kits
factor by
# of HD fiber modules
x 158
# of CU kits
x 222
# of 1U G2 LC kits
x 222
# of 96F LC or MPO kits
x 188
Maximum no. of kits in rack
≤ 10,000