Instruction Sheet:

 SYSTIMAX 360™ iPatch

® 

PATCHMAX

®

 Modular Panel

5

7

After all cables have been connected to the module, remove the 
module and rotate it so the front of the module is facing forward. 
Then install the module in its intended location (where the cables 
were pulled through).

To install a 6-pack module

, gently press the module straight into 

the panel opening until the module snaps into place.

To install a 12-pack module

, position the lower edge of the 

module into the panel opening so the edge of the opening rests 
in the slot along the bottom of the module (Figure 10). Then 
gently press the top of the module until the module snaps into 
place.

8

Reinstall the module(s) that you temporarily removed in Step 3.

9

Repeat Step 1 through Step 8 to cable each module for the 
panel.

10

When all modules have been cabled, reinstall the iPatch sensor 
overlay on the front of the panel (Figure 11):

a

Connect the overlay to the panel bus jumper.

b

Position the overlay on the panel so the hooks on the back of 
the overlay fit into the front of the panel.

c

Slide the overlay to the left so the hooks engage with the 
panel and the buttons align with the ports.

Important: 

For 48-port panels, reinstall both iPatch sensor 

overlays.

Installing the Rear Cable Support (Optional)

The SYSTIMAX 360

™ 

iPatch

®

 PATCHMAX

®

 Modular Panel includes 

rear cable management. When cabling the panel from the front, 
install the cable support first. When cabling the panel from the rear, 
install the cable support after completing cabling.

To assemble and install the rear cable support:

1

Snap the 4 cable troughs onto the cable support bar.

2

Insert the 4 cable straps into the slots in the cable troughs.

3

Hook the cable support bar onto the rear of the panel as shown 
in Figure 12.

4

Route the cables into the cable troughs. Use the cable straps to 
loosely retain the cables (Figure 13).

Figure 10 Reinstalling the Module

Figure 11 Reinstalling the iPatch Sensor Overlay

Panel bus jumpers

Figure 12 Installing the Cable Support

Figure 13 Routing and Retaining the Cables

Cable support bar

Cable trough

Cable strap

Slot

Cable support bar

Summary of Contents for SYSTIMAX 360 iPatch PATCHMAX

Page 1: ... installed GS3 DM or GS5 DM 6 pack or 12 pack modules 4 cabling labels for B wiring 4 or 8 iPatch sensor overlay 1 or 2 panel bus jumper 1 or 2 Patch cord management Front bezel Cable support bar Cable troughs 4 Cable straps 4 12 24 x 1 2 inch screws 4 for mounting the panel in a 19 inch 482 6 mm rack Cabling labels for A wiring 4 or 8 Termination Managers 28 or 56 and instruction sheet Related Co...

Page 2: ... that the labels are oriented with the right side up Figure 1 3 Install the panel on the rack using the 4 screws provided Figure 2 Be careful not to pinch the panel bus jumper s between the panel and rack 4 Connect the panel bus jumper a Remove the adhesive backing from the cable retainers on the panel bus jumper b Connect the panel bus connector on the jumper to the nearest connector on the panel...

Page 3: ...e rear cable support following the instructions in Installing the Rear Cable Support Optional on page 5 Cabling from the Front To cable modules from the front of the panel Important Power must be removed from the rack s Panel Manager when cabling modules for the panel 1 Install the rear cable support following the instructions in Installing the Rear Cable Support Optional on page 5 Note Loosely se...

Page 4: ...backwards position the lower edge of the module into the panel opening so the small tabs hook onto the edge of the opening Figure 8 Then gently press the top of the module until the module snaps into place 5 Pull the cables through the panel opening where the module will be installed and mark the cables for termination leaving an adequate length of cables to reach the module Make sure that the cab...

Page 5: ... the overlay on the panel so the hooks on the back of the overlay fit into the front of the panel c Slide the overlay to the left so the hooks engage with the panel and the buttons align with the ports Important For 48 port panels reinstall both iPatch sensor overlays Installing the Rear Cable Support Optional The SYSTIMAX 360 iPatch PATCHMAX Modular Panel includes rear cable management When cabli...

Page 6: ...Figure 15 and insert the 2 bottom retention tabs into the slots on the patch cord management 3 Pivot the top of the bezel towards the panel until the 3 tabs on the top of the bezel snap into the panel Figure 15 4 Restore power to the rack s Panel Manager How To Contact Us To find out more about SYSTIMAX Solutions visit us on the web at www commscope com systimax For technical assistance regarding ...

Reviews: