background image

5. Extended functions 

16 

5.5.2  Outputs 

 Attention  

The maximum connected loads for the 
programmable outputs (relay contacts) are 1A / 
240V. 

The DELCOS 

Pro

 has two programmable outputs. 

Output 1 is a relay with changeover contact and output 
2 is a relay with NO contact. You can assign (program) 
various functions to the outputs.  

The outputs are programmed in the 

[OPTIONAL

 

IN-

/OUTPUTS]

 sub-menu. Please go to the 

[OPTIONAL

 

IN-/OUTPUTS]

 sub-menu. Then go to 

the 

  

OUTPUT

 

1: FAULT

  menu item 

If you press the   key, the function starts to flash. By 
pressing the 

  

or

 

 

key, you can now change the 

function. Once you have set the function you want, this 
has to be confirmed using the   key. The output is now 
programmed. 

You access the other programmable output by pressing 
the 

  

key. 

When supplied, output 1 is programmed with the 
'

FAULT

' function. Output 2 is not programmed upon 

delivery. Each of the two outputs an be programmed 
with any of the functions listed below. You will also find 
an overview of the inputs and associated functions in 
the machine's circuit diagram. 

Explanation of functions: 

FREE

 

Output is not programmed. 

OPERATING

 

The output (relay) is activated when the compressor's 
motor is switched on or when the compressor is ready. 

ON-LOAD

 

The output (relay) is activated when the compressor is 
in on-load. 

OFF-LOAD

 

The output (relay) is activated when the compressor is 
in off-load. 

FAULT

 

The output (relay) is activated when there are no faults 
on the compressor. 

WARNING

 

The output (relay) is activated when there are no 
warnings on the compressor. 

MAINT.

 

ELAPSED

 

The output (relay) is activated when there are no 
maintenance messages on the compressor. 

 

WARNING/MAINT.

 

The output (relay) is activated when there are no 
warnings and no maintenance messages on the 
compressor. 

WARN/MA/FAULT

 

The output (relay) is activated when there are no 
warnings, no maintenance messages and no faults on 
the compressor. 

REM.STARTABLE

 

The output (relay) is activated when the compressor is 
ready for the remote start. 

RUNNING

 

The output (relay) is activated when the compressor's 
motor is running (is switched on). 

 

5.6  Locking / unlocking code  

Settings (sub-menus) can be locked using a code to 
prevent unauthorised programming. 

Limit values cannot be changed by the operator. 

Locking 

If the code is to be locked, this is done using the 

 

key. 

Please press this key for 5 seconds. The following 
message then appears on the display: 

CODE:

 

UNLOCK

 (for 1 second) 

CODE

 

INPUT 0000

 (

0000

 value flashes) 

If the code: 3031 is entered, the following message 
appears: 

CODE:

 

LOCK

 (for 1 second) 

The sub-menus are now locked and cannot be 
changed. 

If the wrong code is entered, the following message 
appears: 

CODE:

 

UNLOCK

 (for 1 second) 

The display then automatically jumps back to where it 
started from. 

Unlocking 

If the code is to be unlocked again, this either done by: 

*

  pressing (for 5 seconds) the 

 

key when not in the 

menu or  

*

  pressing (for 5 seconds) the 

 

key when attempting 

to change a protected value in a sub-menu. 

The code prompt then appears: 

CODE:

 

LOCK

 (for 1 second) 

CODE

 

INPUT 0000

 (

0000

 value flashes) 

Summary of Contents for DELCOS Pro

Page 1: ...GB Id no 100013596 03 January 2010 1 Original User Manual DELCOS Pro electronics for stationary rotary screw compressor...

Page 2: ......

Page 3: ...1 German basis BA 100013595 03 Valid as of software version DPro L 1 xx We reserve the right to modifications relating to technical advances...

Page 4: ...rogramming maintenance intervals 9 4 3 Total load hours counter 9 5 Extended functions 10 5 1 CONTROL MENU sub menu 10 5 1 1 Operating modes 10 5 1 2 Second pressure range p2 10 5 1 3 Dryer pre run 10...

Page 5: ...al compression pressure is the pressure measured downstream of the compressor stage Network pressure is the pressure within the system connected downstream of the compressor The following symbols may...

Page 6: ...START IN xxs alternating with AFTER POWER LOSS A power loss has caused the unit to shut down The automatic restart function has been selected in the control menu The unit now starts automatically aft...

Page 7: ...0 00 00 p27 __________ 00 00 00 00 01 EM STOP 12345h 01 EM STOP 12300h CUT OUT POINT 13 0bar CUT IN POINT 12 5bar p2 CUT OUT POINT 10 5bar p2 CUT IN POINT 10 0bar AUTOMATIC OPERATION ENABLE REMOTE STA...

Page 8: ...CONTROL MENU FAULT MEMORY TIMER CONTROL LIMIT VALUES OPTIONAL IN OUTPUTS Enter a sub menu by pressing the key Again here you can use the or keys to go to a menu item To exit the sub menu you must pre...

Page 9: ...e set by pressing the key Note The control system checks whether the value set can be used The maximum network pressure CUT OUT POINT must be at least 0 2 more than the minimum network pressure CUT IN...

Page 10: ...requirement from the compressed air system and the unit is in CONTINUOUS OPERATION it switches to OFF LOAD This means that the motor and compressor stage run but no air is pumped into the compressed...

Page 11: ...maintenance interval should be reprogrammed The maintenance message can be acknowledged using the key 4 2 Programming maintenance intervals To program a maintenance interval please go to the MAINTENAN...

Page 12: ...second pressure range function in the CONTROL MENU sub menu The relevant menu items there are p2CUT OUT POINT 10 5bar p2CUT IN POINT 10 0bar p2TIMER CONTROL OFF You can use p2CUT OUT POINT and p2CUT I...

Page 13: ...it features several compressors This in turn ensures that the power supply is not loaded unnecessarily 5 1 6 Unlimited autom re start after power loss The control system can perform an automatic re st...

Page 14: ...sion pressure and network pressure When accessed these values flash to clearly show that they are not the current display values To access this information please use or to go to the warning message o...

Page 15: ...entry The timer is now switched on To improve your understanding of this function the timer unit setting is explained below using various examples Example 1 Switching unit 1 not active 1 _______ 00 0...

Page 16: ...for the 2nd pressure range 5 4 Limit values sub menu The LIMIT VALUES sub menu is for information only Here you can access the parameters set in the factory The following are shown a DESIGN PRESS 13 0...

Page 17: ...not assigned programmed EXT FAULT If the contact is opened the EXT FAULT fault message appears on the display and the unit is shut down shutting down is delayed by 1sec EXT WARNING If the contact is...

Page 18: ...e no faults on the compressor WARNING The output relay is activated when there are no warnings on the compressor MAINT ELAPSED The output relay is activated when there are no maintenance messages on t...

Page 19: ...ed twice for codes 2 and 3 If you have entered a code incorrectly the indication immediately jumps back to code 1 You then have to re enter all three codes If you have correctly entered the codes the...

Page 20: ...AD Fig 5 Circuit diagram for pressure changeover Sections 5 1 2 and 5 3 2 contain explanations of how to set the second pressure range and the possibility of timer operations with the second pressure...

Page 21: ...now be switched to on load or off load using these two inputs You will find a circuit diagram in Fig 6 In our explanation we have assigned the inputs as follows INPUT 1 ENAB REM LOAD INPUT 2 REMOTE L...

Page 22: ...e key to change the value to ON The symbol appears in the first display row Please connect the potential free contact that you need for the remote start stop function to the X2 1 and X2 3 terminals Th...

Page 23: ...must not exceed 55 C 4 All remote controls fitted at a later date remote On Off must be managed without a connection relay at max 20 metres from the control cabinet 5 When commissioning and carrying...

Page 24: ...tive cooling Improve Unit being operated with enclosure open Close enclosure Oil injection volume temperature too low high Check find cause Incorrect oil grade viscosity Check replace oil if necessary...

Page 25: ...PUT EXT WARNING 3 Check find cause FAULT BEKOMAT FAULT Connected condensate drain valve Bekomat defective 3 Check find cause WARNING BEKOMAT WARN Connected condensate drain valve Bekomat defective 3 C...

Page 26: ...ef pressure requirements during the run on time No compressed air requirements within the switching points set 4 Pressure changeover by timer or external contact active 5 1 Unit specific setting see 5...

Page 27: ......

Page 28: ...Gardner Denver Deutschland GmbH Argenthaler Str 11 55469 Simmern Germany Tel 49 0 6761 832 0 www compair com e mail sales compair com...

Reviews: