background image

2. Default settings 

Defa ult  set tin gs 

2.1  Selecting language 

You can change the language by pressing the   + 

  

 

or   +

 

 keys. Press these keys at the same time until 

the right language appears. 

 
 

2.2  Setting network pressure 

The compressor is controlled using an electronic 
pressure switch. In the 

[

 

CONTROL

 

MENU

 

]

 menu you 

have to set the minimum network pressure switching 
point (

CUT-IN

 

POINT

) and the maximum network 

pressure switching point (

CUT-OUT

 

POINT

). 

When the maximum network pressure switching point is 
reached, the machine switches to off-load. 

The minimum network pressure switching point then 
specifies when the machine is switched back into on-
load. 

Example: 

CUT-OUT

 

POINT  10.0bar  

CUT-IN

 

POINT 

9.8bar  

When the network pressure reaches 10.0 bar, the 
machine switches to off-load. 

If the network pressure then falls to 9.8 bar, the 
machine is switched back into on-load. 

Max. network pressure: 

The network pressure is set in the 

 

[

 

CONTROL

 

MENU

 

  sub-menu. The 

  

+

 

 

 keys -

have to be pressed at the same time to do this. You are 
then taken to the main menu. Use 

 

  

 to switch to the 

 

[

 

CONTROL

 

MENU

 

]

 sub-menu. Then please press the 

 key. 

 

The 

 CUT-OUT

 

POINT

 menu item now appears on the 

display. Again pressing the 

  key causes the value to 

flash. You can now correct (increase or decrease) this 
value using 

  

or

 

 

. Then confirm the value set by 

pressing the   key. 

 

Note  

The control system checks whether the value set can 
be used. The maximum network pressure 

 CUT-

OUT

 

POINT 

must be at least 0.2 more than the 

minimum network pressure 

CUT-IN

 

POINT.

 You may 

therefore have to first set the minimum network 
pressure point. To prevent your compressor suffering 
from excess wear, the difference between the 

CUT-

OUT

 

POINT 

and 

CUT-IN

 

POINT 

should not be too 

small. 

 

Min. network pressure: 

In the 

 [

 

CONTROL

 

MENU

 

sub-menu please use 

 

 

to go to the 

 CUT-IN

 

POINT

 menu item. 

Pressing the   key causes the value to flash.

 

You can now correct (increase or decrease) this value 
using 

  

or

 

 

. Then confirm the value set by pressing 

the   key. 

 
 
 

CUT-OUT POINT 
CUT-IN POINT  

 

 

 

ON-LOAD 

 

Pressure switch 

 

 

 
 
 

Fig. 1  Block diagram 

 
 

2.3  Setting time/date (timer) 

The DELCOS 

Pro

 accumulator can bridge a loss of 

power lasting between around two to three weeks. If 
power is lost for longer periods, the timer's time and 
date are lost and have to be entered anew. 

Press the 

  

+

 

 

 keys at the same time. Use 

 

 

 to go 

to the 

[

 

TIMER

 

CONTROL

 

sub-menu and press the 

 key. The date and time are displayed there in the 

following format: 

TU 30.10.07 12:10:34 

If you press the   key, the left-hand value (day of the 
week) starts to flash. You can now use the 

  

or

 

 

 

keys to set this. Then confirm the value by pressing the 

 key.  

All values can now be set in succession using this 
procedure. When the last value (seconds) has been 
set, the timer is fully set and you can exit the menu by 
twice pressing the 

  

+

 

 

 keys at the same time.  

Summary of Contents for DELCOS Pro

Page 1: ...GB Id no 100013596 03 January 2010 1 Original User Manual DELCOS Pro electronics for stationary rotary screw compressor...

Page 2: ......

Page 3: ...1 German basis BA 100013595 03 Valid as of software version DPro L 1 xx We reserve the right to modifications relating to technical advances...

Page 4: ...rogramming maintenance intervals 9 4 3 Total load hours counter 9 5 Extended functions 10 5 1 CONTROL MENU sub menu 10 5 1 1 Operating modes 10 5 1 2 Second pressure range p2 10 5 1 3 Dryer pre run 10...

Page 5: ...al compression pressure is the pressure measured downstream of the compressor stage Network pressure is the pressure within the system connected downstream of the compressor The following symbols may...

Page 6: ...START IN xxs alternating with AFTER POWER LOSS A power loss has caused the unit to shut down The automatic restart function has been selected in the control menu The unit now starts automatically aft...

Page 7: ...0 00 00 p27 __________ 00 00 00 00 01 EM STOP 12345h 01 EM STOP 12300h CUT OUT POINT 13 0bar CUT IN POINT 12 5bar p2 CUT OUT POINT 10 5bar p2 CUT IN POINT 10 0bar AUTOMATIC OPERATION ENABLE REMOTE STA...

Page 8: ...CONTROL MENU FAULT MEMORY TIMER CONTROL LIMIT VALUES OPTIONAL IN OUTPUTS Enter a sub menu by pressing the key Again here you can use the or keys to go to a menu item To exit the sub menu you must pre...

Page 9: ...e set by pressing the key Note The control system checks whether the value set can be used The maximum network pressure CUT OUT POINT must be at least 0 2 more than the minimum network pressure CUT IN...

Page 10: ...requirement from the compressed air system and the unit is in CONTINUOUS OPERATION it switches to OFF LOAD This means that the motor and compressor stage run but no air is pumped into the compressed...

Page 11: ...maintenance interval should be reprogrammed The maintenance message can be acknowledged using the key 4 2 Programming maintenance intervals To program a maintenance interval please go to the MAINTENAN...

Page 12: ...second pressure range function in the CONTROL MENU sub menu The relevant menu items there are p2CUT OUT POINT 10 5bar p2CUT IN POINT 10 0bar p2TIMER CONTROL OFF You can use p2CUT OUT POINT and p2CUT I...

Page 13: ...it features several compressors This in turn ensures that the power supply is not loaded unnecessarily 5 1 6 Unlimited autom re start after power loss The control system can perform an automatic re st...

Page 14: ...sion pressure and network pressure When accessed these values flash to clearly show that they are not the current display values To access this information please use or to go to the warning message o...

Page 15: ...entry The timer is now switched on To improve your understanding of this function the timer unit setting is explained below using various examples Example 1 Switching unit 1 not active 1 _______ 00 0...

Page 16: ...for the 2nd pressure range 5 4 Limit values sub menu The LIMIT VALUES sub menu is for information only Here you can access the parameters set in the factory The following are shown a DESIGN PRESS 13 0...

Page 17: ...not assigned programmed EXT FAULT If the contact is opened the EXT FAULT fault message appears on the display and the unit is shut down shutting down is delayed by 1sec EXT WARNING If the contact is...

Page 18: ...e no faults on the compressor WARNING The output relay is activated when there are no warnings on the compressor MAINT ELAPSED The output relay is activated when there are no maintenance messages on t...

Page 19: ...ed twice for codes 2 and 3 If you have entered a code incorrectly the indication immediately jumps back to code 1 You then have to re enter all three codes If you have correctly entered the codes the...

Page 20: ...AD Fig 5 Circuit diagram for pressure changeover Sections 5 1 2 and 5 3 2 contain explanations of how to set the second pressure range and the possibility of timer operations with the second pressure...

Page 21: ...now be switched to on load or off load using these two inputs You will find a circuit diagram in Fig 6 In our explanation we have assigned the inputs as follows INPUT 1 ENAB REM LOAD INPUT 2 REMOTE L...

Page 22: ...e key to change the value to ON The symbol appears in the first display row Please connect the potential free contact that you need for the remote start stop function to the X2 1 and X2 3 terminals Th...

Page 23: ...must not exceed 55 C 4 All remote controls fitted at a later date remote On Off must be managed without a connection relay at max 20 metres from the control cabinet 5 When commissioning and carrying...

Page 24: ...tive cooling Improve Unit being operated with enclosure open Close enclosure Oil injection volume temperature too low high Check find cause Incorrect oil grade viscosity Check replace oil if necessary...

Page 25: ...PUT EXT WARNING 3 Check find cause FAULT BEKOMAT FAULT Connected condensate drain valve Bekomat defective 3 Check find cause WARNING BEKOMAT WARN Connected condensate drain valve Bekomat defective 3 C...

Page 26: ...ef pressure requirements during the run on time No compressed air requirements within the switching points set 4 Pressure changeover by timer or external contact active 5 1 Unit specific setting see 5...

Page 27: ......

Page 28: ...Gardner Denver Deutschland GmbH Argenthaler Str 11 55469 Simmern Germany Tel 49 0 6761 832 0 www compair com e mail sales compair com...

Reviews: