CompAir Limited
page 22
When the compressor is piped into an existing
rigidly fixed compressed air main the length of pipe
between the compressor delivery flange and the
nearest fixed support should be at least 3 m. This
connecting pipe must include a 90° bend of 0.3 m
minimum radius with a straight vertical length of pipe
of at least 1.2 m between the compressor delivery
flange and the bend.
When an aftercooler is installed in a system
incorporating an air receiver, the aftercooler should
be between the compressor and the receiver. If a
non-return valve is incorporated, this should be
upstream of the aftercooler. If the aftercooler is
positioned close to the compressor the connecting
pipework will normally be in the form of an inverted U
loop and one vertical leg of the loop must be at least
1.2 m in length. The connection between the
aftercooler and the air receiver must be arranged as
in the previous paragraph.
It is essential that all pipework is made and installed
so that it is not constrained or distorted when
connected to the compressor, aftercooler or user's
pipework. Use 90° bends with 0.3 m minimum
radius. Do NOT use elbows.
Where the installation includes a water cooled
intercooler and/or aftercooler, valves must be
installed in the water inlet and outlet pipes to allow
the compressor and the aftercooler to be isolated
from the water supply. If the compressor is to
operate under automatic start/stop control the
isolating valves on the inlet pipes should be solenoid
operated and the solenoids interconnected with the
compressor starter. This will ensure that the water
supply is cut off when the compressor shuts down
or is on standby.
If the compressor is operating under air governor
control fit 'Iockshield' valves in the water inlet pipes
to the intercooler and aftercooler to allow control of
cooling water flow. This is particularly important in
multiple installations.
Where necessary the cooling water system must be
protected to prevent freezing.
If the compressor is connected into a central cooling
system check that the cooling water is of good
quality.
Whenever cooling towers are used in the water
cooling system expert advice must be sought
regarding the precautions to be taken to prevent the
development of harmful bacterial growth which could
cause a health hazard.
On installations equipped with individual cooling
towers the power supply to the water pump and the
cooling tower fan must be interlocked with the
compressor starter. The operation of the cooling
tower fan should also be controlled by a suitable
thermostat fitted in the cooling tower sump.
It is recommended that the pipe from the
condensate valve should lead to the disposal
system by way of an open drain or tundish so that
valve operation may be observed.
If an air dryer is installed with the compressor it
should be located downstream of the air receiver.
Bypass valves and piping should be fitted so that
the dryer may be isolated for servicing. If the dryer is
of the desiccant type a prefilter and an afterfilter
must be incorporated, particularly if used with a
lubricated compressor.
Summary of Contents for EO40/0001
Page 12: ...CompAir Limited page 10...
Page 16: ...CompAir Limited page 14...
Page 17: ...page 15 V100 VL400 User Manual 3 LEADING PARTICULARS...
Page 39: ...page 37 V100 VL400 User Manual 7 FAULT FINDING...
Page 44: ...CompAir Limited page 42...
Page 45: ...page 43 V100 VL400 User Manual APPENDIX 1 The Pressure Systems Safety Regulations 2000...
Page 48: ...CompAir Limited page 46...