page 23
V100-VL400 User Manual – Installation
Room volume
Additional area
Model
Room volume with aftercooler
to inlet opening
7 bar
10.5 bar
for aftercooler
m
3
m
3
m
2
m
2
m
2
V100A 29
43
0.45
0.55
0.25
V100W 29
- 0.45
0.55
-
V100DA 29
43
0.45
0.55
0.25
V100DW 29
-
0.45
0.55
-
V150A 43
64
0.7
0.8
0.4
V150W 43
- 0.7
0.8
-
V150DA 43
64
0.7
0.8
0.4
V150DW 43
-
0.7
0.8
-
V200A 57
85
0.9
1.05
0.5
V200W 57
- 0.9
1.05
-
V200DA 57
85
0.9
1.05
0.5
V200DW 57
-
0.9
1.05
-
VL200A 29
57
0.4
VL200DA 29
57
0.4
V300A 85
128
1.3
1.5
0.8
V300W 85
- 1.3
1.5
-
V300DA 85
128
1.3
1.5
0.8
V300DW 85
-
1.3
1.5
-
VL300A
43
85
- - -
VL300DA
43
85
- - -
VL400A
57
114
- - -
VL400DA
57
114
- - -
Total area of ventilation
inlet and outlet openings
0.4 (up to 2.5 bar only)
0.4 (up to 2.5 bar only)
3.
VENTILATION
In operation the compressor will release heat into the surroundings and therefore the compressor room should
be of adequate size and have good ventilation. The recommended minimum sizes of room and ventilation
openings are as below:
If any difficulties are anticipated or if there are space limitations on site consult the local CompAir distributor
before installation is commenced.
Summary of Contents for EO40/0001
Page 12: ...CompAir Limited page 10...
Page 16: ...CompAir Limited page 14...
Page 17: ...page 15 V100 VL400 User Manual 3 LEADING PARTICULARS...
Page 39: ...page 37 V100 VL400 User Manual 7 FAULT FINDING...
Page 44: ...CompAir Limited page 42...
Page 45: ...page 43 V100 VL400 User Manual APPENDIX 1 The Pressure Systems Safety Regulations 2000...
Page 48: ...CompAir Limited page 46...