Figure 12

. High-density system with conventional cooling 

 

 

 

 

 

 

UPS 

rack 

ITE 

racks 

Distribution 

cables 

From 

AC Mains 

Power 

distribution 

rack 

 

 

High-density system using chilled-water cooling 

Figure 13 shows a high-density system of two 30-kW ITE racks powered from a UPS rack of parallel 
HP RP12000/3 UPSs to provide 60 kilowatts of power distributed through the HP PDR. In this 

example, the HP Modular Cooling System (MCS) is used to provide chilled-water, forced-air cooling 

for the IT equipment. The UPSs and PDR use conventional cooling methods. Cabling is routed 

overhead in cable trays (not shown) and through the tops of the racks. This configuration is possible in 
facilities with raised or non-raised floors. 

 

Figure 13.

 High-density system with the HP MCS 

ITE racks 

with HP MCS 

 

 

From 

AC Mains 

Distribution 

cables 

Power 

distribution 

rack 

UPS 

rack 

 

 

 

12

 

Summary of Contents for 204451-002 - UPS T2200 XR

Page 1: ...PS load considerations 5 UPS topologies single conversion versus double conversion 6 HP solution high efficiency three phase UPSs 7 Three phase power distribution technology 8 Load balancing and monit...

Page 2: ...al load properly with facility power to ensure safe and cost efficient operation Power distribution in data centers The typical data center uses power that originates from the utility power grid and i...

Page 3: ...tery power until utility power is restored to within the accepted operating range or until the building generator can produce the required power whichever comes first Once UPS input power resumes eith...

Page 4: ...fits of distributing three phase power to individual racks become more significant Strictly speaking IT equipment ITE does not use three phase power1 the benefits are in its distribution These benefit...

Page 5: ...erated by most power supply units is typically within the 47 to 64 Hz range to accommodate worldwide applications UPS must maintain output frequency within the acceptable range Power factor correction...

Page 6: ...gure 4B includes a rectifier In normal operation the rectifier processes the AC input voltage and routes the DC to the inverter that produces the output In online operation the batteries provide the i...

Page 7: ...t that meets load requirements When AC input power is absent the system goes into battery mode Figure 5 HP RP12000 3 UPS Figure 6 DCOD topology used in HP three phase UPSs One characteristic of the DC...

Page 8: ...o 85 percent efficiency at the same loading Three phase power distribution technology The benefits of distributing three phase power to individual racks become significant for high density installatio...

Page 9: ...planning Racks receiving two AC buses will require power distribution units PDUs to be installed in pairs to achieve a balance of equipment loading With three phase distribution each equipment rack re...

Page 10: ...ferent levels of load monitoring Circuit monitoring panel provides local display of current loading at the distribution panel level Enhanced monitoring provides local display of current demand voltage...

Page 11: ...60 kilowatts through a PD rack and power distribution cables to a high density system of four 15 kW ITE racks In this example the ITE racks use conventional air cooling as supplied through plenums in...

Page 12: ...ts of power distributed through the HP PDR In this example the HP Modular Cooling System MCS is used to provide chilled water forced air cooling for the IT equipment The UPSs and PDR use conventional...