background image

 

Three-phase UPS technology 

The main purpose of the UPS is to maximize the availability of IT equipment by providing a constant 

power source for IT equipment, regardless of the state of the AC power the UPS receives. UPS 

performance is determined by its design parameters and topology. 

UPS load considerations 

A UPS should be designed based on two main factors: the AC input feed, and the needs and 
characteristics of the active output load. In this case, the active output load is comprised of the power 

supply units (PSUs) of the IT equipment. Table 1 identifies the primary PSU parameters to which a UPS 

must be designed. 

Table 1

. Primary parameters of power supply units that affect UPS design  

PSU parameter 

Parameter description 

UPS design criteria 

AC input 

voltage  

Typically low-line (100 to 127 VAC) 
or high-line (200 to 240 VAC) input 
power. High-density server systems 

often use power supplies that can 

operate with either low-line or high-
line power, but require high-line 

power to operate at maximum rated 

performance and peak efficiency. 

UPS must maintain a three-phase output with 
single-phase and split-phase components 
that meet the acceptable range of the power 

supply units. 

AC input 

frequency 

Frequency tolerated by most power 
supply units is typically within the 47 
to 64 Hz range to accommodate 

worldwide applications. 

UPS must maintain output frequency within 

the acceptable range 

Power factor 

correction 

Power supply circuitry that 
compensates for the power loss 
inherent with reactive components 

using AC voltage   

The cumulative power requirement of all 
power supply units in a circuit branch should 
not exceed UPS volt-ampere (VA) and watt 

(W) ratings 

Ride-through 
capability 

(holdup time) 

Ability of a power supply unit to 
provide rated output during an AC 
power interruption, typically 12 to 

20 ms. 

UPS mode transitions (offline-to-online, 
online-to-offline) need to occur much faster (5 
ms or less) than the power supply unit 

holdup time to ensure constant operation of 

power supply unit. 

AC line 
transient 

handling 

Ability of a power supply unit to 
absorb AC line sags (brownouts) and 

surges (spikes) 

UPS must prevent passing on AC line 
transients that would adversely affect power 

supply units.  

 
In addition, the UPS must meet the cumulative power consumption of all power supply units included 

in the output circuit. While UPS specifications generally include both volt-amperes (VA) and watt (W) 

ratings, the rating in watts provides a truer indication of the loading ability of the UPS. The watts 

rating will be stated with a time parameter indicating how long the UPS can provide the rated power 
in the online (battery) mode. 

5

 

Summary of Contents for 204451-002 - UPS T2200 XR

Page 1: ...PS load considerations 5 UPS topologies single conversion versus double conversion 6 HP solution high efficiency three phase UPSs 7 Three phase power distribution technology 8 Load balancing and monit...

Page 2: ...al load properly with facility power to ensure safe and cost efficient operation Power distribution in data centers The typical data center uses power that originates from the utility power grid and i...

Page 3: ...tery power until utility power is restored to within the accepted operating range or until the building generator can produce the required power whichever comes first Once UPS input power resumes eith...

Page 4: ...fits of distributing three phase power to individual racks become more significant Strictly speaking IT equipment ITE does not use three phase power1 the benefits are in its distribution These benefit...

Page 5: ...erated by most power supply units is typically within the 47 to 64 Hz range to accommodate worldwide applications UPS must maintain output frequency within the acceptable range Power factor correction...

Page 6: ...gure 4B includes a rectifier In normal operation the rectifier processes the AC input voltage and routes the DC to the inverter that produces the output In online operation the batteries provide the i...

Page 7: ...t that meets load requirements When AC input power is absent the system goes into battery mode Figure 5 HP RP12000 3 UPS Figure 6 DCOD topology used in HP three phase UPSs One characteristic of the DC...

Page 8: ...o 85 percent efficiency at the same loading Three phase power distribution technology The benefits of distributing three phase power to individual racks become significant for high density installatio...

Page 9: ...planning Racks receiving two AC buses will require power distribution units PDUs to be installed in pairs to achieve a balance of equipment loading With three phase distribution each equipment rack re...

Page 10: ...ferent levels of load monitoring Circuit monitoring panel provides local display of current loading at the distribution panel level Enhanced monitoring provides local display of current demand voltage...

Page 11: ...60 kilowatts through a PD rack and power distribution cables to a high density system of four 15 kW ITE racks In this example the ITE racks use conventional air cooling as supplied through plenums in...

Page 12: ...ts of power distributed through the HP PDR In this example the HP Modular Cooling System MCS is used to provide chilled water forced air cooling for the IT equipment The UPSs and PDR use conventional...

Page 13: ...T equipment and power distribution products from different sources to build a complete datacenter There were always concerns of how easily efficiently and reliably components from different vendors wo...

Page 14: ...er white papers http h18004 www1 hp com products servers technology whit epapers datacenter html Call to action Send comments about this paper to TechCom HP com 2007 Hewlett Packard Development Compan...

Reviews: